GE VersaMax IC200ALG630 User Manual

GE VersaMax IC200ALG630
5 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
VersaMax* Analog Input, 16-Bit Thermocouple Module
IC200ALG630
October 2016 GFK-1700L
1
Product Description
The IC200ALG630 Analog Input Thermocouple Module is an intelligent
module that accepts seven independent thermocouple or millivolt inputs.
The module receives power from the backplane power supply. No
external power source is required.
1234567 831
ANALOG INPUT 16BIT
THERMOCOUPLE 7CH
OK
Each input channel can be configured to report millivolts ranges as
1/100 of millivolts, or thermocouple inputs as linearized temperature in
tenths of degrees Celsius or Fahrenheit, with or without cold junction
compensation.
The module automatically performs A/D calibration at powerup.
Automatic calibration is then repeated periodically to compensate for
changes in the ambient temperature. New calibration values are filtered
into the current calibration values.
Host Interface
The Analog Input Thermocouple Module uses the following data types:
7 words of analog input data.
7 optional words of analog output data.
The module exchanges data in the same manner as other types of I/O
modules: it provides all its input data when requested.
Diagnostics
The Analog Input Thermocouple Module performs diagnostics and
provides the following information.
Alarm faults are reported if the processed value for a channel
exceeds its configured alarm limit.
Over/underrange faults are reported if the millivolt value for an
input exceeds the limits of its span.
Open circuit is checked every time a thermocouple input is read
(unless Open TC checking is disabled). If the circuit is open, a fault
is reported and the input defaults to the configured channel default.
Thermistor fault will be reported as Internal fault in the I/O Fault
table.
A thermistor fault occurs if the calculated temperature value from the
thermistor is less than -10 °C or greater than +75 °C.
LED Indicators
The green OK LED is on when backplane power is present to the
module. If this LED is amber, it indicates a module fault.
Module Characteristics
Channels
Seven thermocouple or millivolt inputs
Module ID
FFFF9804
Isolation:
User input to logic
(optical) and to frame
ground
Group to group
Channel to channel
250VAC continuous; 1500VAC for 1 minute
Not applicable
None
LED indicators
OK LED: Green indicates backplane power is
present. Amber indicates module fault.
Backplane current consumption
5V output: 125mA maximum. 3.3V output: 125mA
maximum.
External power supply
None
Thermal derating
None
Diagnostics
Open Thermocouple, over/under range, and
high/low alarm, thermistor fault (reported as
internal fault).
Input Characteristics
Thermocouple types
J, K, T, S, R, none (used for mV inputs)
Spans (+/)
19.5mV, 39mV, 78.125mV, 156.25mV, 312.5mV,
625mV
Converter resolution
15 bits + sign
Cold junction compensation
If used, reference junction temperature is
measured at thermocouple termination using a
precision thermistor, or supplied by system, or by
fixed configuration value.
Cold junction temperature error
+/0.25 degree Celsius (local measurement). To
reduce temperature transients, thermocouple
terminations should not be installed in the same
cabinet as heat dissipation assemblies.
Conformity error
+/0.3 degree Celsius, +/0.5 degree Fahrenheit.
Accuracy, at 25° C
on voltage measurement:
on temp. measurement:
+/0.2%
+/- 3 degrees Celsius.
Temperature sensitivity
(0° to 60°C)
+/0.004% of reading, +/1.5µV per ° Celsius
referred to input
Normal mode rejection
60dB, at 50/60 Hz, 100% span
Common mode rejection
120 dB at 50/60Hz, 100 ohm imbalance
Common mode voltage
3 VDC maximum
Maximum voltage between
channels
50V
Normal mode voltage
5 VDC maximum
Scan time
60 Hz: approximately 60 milliseconds per point
50 Hz: approximately 70 milliseconds per point.
Preinstallation Check
Carefully inspect all shipping containers for damage. If any equipment
is damaged, notify the delivery service immediately. Save the
damaged shipping container for inspection by the delivery service.
After unpacking the equipment, record all serial numbers. Save the
shipping containers and packing material in case it is necessary to
transport or ship any part of the system.
Question and Answer IconNeed help?

Do you have a question about the GE VersaMax IC200ALG630 and is the answer not in the manual?

GE VersaMax IC200ALG630 Specifications

General IconGeneral
BrandGE
ModelVersaMax IC200ALG630
CategoryControl Unit
LanguageEnglish

Summary

Product Description

Host Interface

Details the data types and exchange method for the Analog Input Thermocouple Module.

Diagnostics

Outlines the diagnostic capabilities and fault reporting mechanisms of the module.

LED Indicators

Explains the meaning of the module's status indicators, specifically the OK LED.

Module Characteristics

Module Characteristics - LED Indicators

Details the function of the OK LED, indicating backplane power and module fault status.

Input Characteristics

Preinstallation Check

Installation Instructions

Installation in Hazardous Locations

Provides safety guidelines and warnings for installing the module in hazardous locations.

Field Wiring Terminals

Lists the terminal assignments for the module's field wiring connections.

Wiring Connections for Carriers with Two Rows of Terminals

Illustrates the wiring connections for carriers that feature two rows of terminals.

Wiring Connections for Carriers with Three Rows of Terminals

Illustrates the wiring connections for carriers that feature three rows of terminals.

Cable Shield Connections

Provides guidance on connecting cable shields to maintain signal integrity.

Product Version Information

Restrictions and Open Issues

Operational Notes

Configuration

Configurable Features

Explains features that can be software-configured, such as channel activation and alarm limits.

Thermocouple Limits

Lists millivolt and temperature limits for various supported thermocouple types.

Cold Junction Compensation

Details the four available options for cold junction compensation.

Range Selection

Describes the six configurable millivolt input ranges available for the module.