g 
Product Data Sheet – rev 4.2 
July 4th 2003  
Page 16 
 
 
 
LightSpeed
  
With Xtream 
CT Scanner System 
GE Medical Systems-America 
Milwaukee, USA  - Fax: 1 414 544 3384 
GE Medical Systems-Asia: 
Tokyo, Japan - Fax: 81 425 85 5490 
Hong Kong - Fax: 852 2559 3588 
GE Medical Systems-Europe 
 
 Minimum Allowance 
Subsystem Watts BTU/hr 
Gantry 5,440  18,600** 
Table 200 700 
PDU 1,000 3,400 
Operator 
Console 
2,165 7,400 
Optional Laser 
Camera 
800 2,730 
 
Recommended cooling values should not be 
used for calculating system input power 
requirements. 
** Recommended Allowance:  7,150/24,400 
 Growth Allowance:   9,200/31,400 
System Components Dimensions 
      mm  inches 
Gantry: 
 Width: 2,230 87.6 
 Depth: 1,007 39.6 
 Height: 1,887 74.1 
Table: 
 Width: 610 24 
 Length: 5,050 199 
 Height: 1,120 44 
Power Distribution Unit: 
 Width: 762 30 
 Depth: 585 23 
 Height: 1,270 50 
Operator Console: 
 Width: 1,238 48.7 
 Depth: 1,288 50.7 
 Height: 1,257 49.5 
Warranty 
The published Company warranty in effect on 
the date of shipment shall apply. The 
Company reserves the right to make changes. 
All specifications are subject to change. 
Regulatory Compliance 
This product is designed to comply with 
applicable standards under the Radiation 
Control for Health and Safety Act of 1968. 
Laser alignment devices contained within this 
product are appropriately labeled according to 
the requirements of the Center for Devices 
and Radiological Health. 
This product is a CE-compliant device which 
satisfies regulations regarding Electro-
Magnetic Compatibility (EMC) and Electro-
Magnetic Interference (EMI), pursuant to IEC-
601. 
 
 
 
 
* Option