GE Limitamp CR194 - Motor Connection Guidelines

GE Limitamp CR194
34 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CR
194
Vacuum
Limitamp
400
Ampere
Control
Motor
Connections
Motor
cables
may
enter
from
the
top
or
bottom
of
the
enclosure
.
In
the
one
-
high
enclosure
,
the
motor
termi
-
nals
arc
located
on
the
inside
lower
left
wall
as
shown
in
Figure
36
.
The
incoming
leads
should
be
trained
for
maximum
space
between
phases
and
ground
.
The
connections
may
be
made
before
or
after
energizing
the
main
bus
and
without
shutting
down
adjacent
equip
-
ment
.
Also
see
Figure
60
.
Warning
:
If
the
main
bus
in
energized
while
load
cables
are
be
-
ing
installed
,
all
barriers
must
be
in
place
and
the
disconnect
switch
must
be
in
the
off
position
and
the
blades
must
be
visu
-
ally
checked
to
ensure
that
they
are
completely
disconnected
from
the
vertical
bus
.
The
motor
terminals
can
accommodate
up
to
one
500
-
MCM
per
phase
with
stress
cones
in
the
standard
26
-
inch
wide
enclosure
.
If
larger
cable
entries
are
required
,
an
optional
84
-
inch
wide
cabinet
is
available
.
Figure
36
.
Load
terminals
located
on
the
left
wall
of
the
high
-
voltage
compartment
.
The
lower
incoming
line
barrier
and
Isolator
switch
barrier
have
been
removed
.
Phase
A
is
at
the
top
.
19
Courtesy of NationalSwitchgear.com