CR
194
Vacuum
Limitamp
400
Ampere
Control
2
.
Prepare
the
cable
for
termination
in
accordance
with
the
manufacturer
s
instructions
.
For
suggested
terminat
-
ing
methods
,
see
pages
20
through
23
and
Figures
39
through
45
.
3
.
Bolt
the
cable
terminals
to
the
bus
or
other
point
of
termination
.
COPPER
LUG
GE
NO
.
0380
TAPE
INSIDE
FOR
RUBBER
OR
NO
.
092
VC
TAPE
FOR
VARNISHED
CAMBRIC
IS
RECOMMENDED
.
ALTERNATE
:
BUILD
ENTIRE
END
SEAL
WITH
GE
IRRASIL
®
TAPE
.
OUTER
LAYER
IRRASIL
TAPE
NOTE
:
FOR
DETAILS
OF
END
SEAL
SEE
FIG
.
40
FOR
&
RUBBER
CABLE
AND
FIG
.
41
FOR
VARNISHED
CAMBRIC
CABLE
.
MIN
4
"
»
|
'
IN
-
FILL
WITH
SEALING
COMPOUND
2
"
1
CABLE
LUG
JUQ
GE
IRRASIL
'
5
'
NO
.
42005
TAPE
m
i
>
*
*
_
Txzi
CABLE
TERMINATOR
FITTING
o
7
/
GE
IRRASIL
®
NO
.
42205
TAPE
GE
NO
.
8380
CABLE
INSULATION
SPLICE
TAPE
Figure
42
.
Termination
of
interlocked
-
armor
,
non
-
shielded
,
5000
-
volt
cable
.
Figure
40
.
Termination
of
rubber
-
insulated
,
non
-
shielded
,
non
-
lead
-
covered
,
5000
-
volt
cable
.
6
"
1
*
W
END
OF
BRAID
Irrasil
No
.
42005
taps
Irra
»
iI
No
.
42005
ta
po
H
3
/
4
"
h
~
rir
?
%
*
O
j
1
/
2
"
I
!
RAID
*
CABLE
TAPE
i
J
-
j t
-
-
-
t
CABLE
INNER
INSULATION
END
SEAL
1
.
Cut
cable
to
proper
length
leaving
conductor
sufficiently
long
to
extend
Into
the
terminal
lug
.
2
.
Remove
braid
,
tape
,
and
Inner
insulation
and
expose
the
conductor
end
for
a
distance
of
one
Inch
plus
the
length
of
conductor
to
go
Into
the
terminal
lug
.
3
.
Attach
terminal
to
conductor
.
4
.
Taper
the
Insulation
as
shown
.
5
.
Remove
the
braid
and
tape
,
if
any
,
six
Inches
from
the
lug
,
exposing
the
Insulation
.
Leave
one
-
half
inch
of
original
cable
tape
extending
beyond
the
cutback
braid
.
6
.
Apply
the
end
seal
using
GE
Irrasil
®
electrical
tape
.
Ob
-
tain
a
smooth
wrapping
but
do
not
stretch
tape
more
than
necessary
.
7
.
Bind
down
end
of
braid
and
tape
,
If
any
,
with
Irrasil
tape
as
shown
on
drawing
.
8
.
Apply
two
layers
half
-
lap
of
GE
Irrasil
®
tape
over
all
from
lug
to
exposed
braid
.
Figure
43
.
Termination
of
Interlocked
-
armor
,
shielded
,
5000
-
volt
cable
.
Figure
41
.
Termination
of
varnished
-
cambric
-
insulated
,
non
-
shielded
,
non
-
lead
-
covered
,
5000
-
volt
cable
.
21
Courtesy of NationalSwitchgear.com