MDS 05-7280A01, Rev. A MDS TransNEXT Technical Manual 49
Table 3-2. OTA broadcast speed controls:
Speed
setting
Transmission
Sequence
Repeat Count
Inter-Message
Delay
robust
20
5 ms
slow
10
50 ms
medium
5
100 ms
fast
2
150 ms
turbo
2
200 ms
The line below initiates the broadcast FW OTA operation from the master at the desired speed using
previously set values for “method” and “reboot. The parameter following start is the speed argument
shown in the table below:
>app_ota start robust
OK
Querying status at the Master will then show:
>app_ota
Status: Active: 0%
To terminate a session at the Master use the “stop” argument on the command line:
>app_ota stop
OK
Checking status will show the following:
>app_ota
Status: Canceled
NOTE Avoid frequent queries on the UI during reprogramming especially when using the faster
transmission selections. It may interfere with successful transfer.