5 CURRENT SETTING THRESHOLD SELECTION
The Phase Overcurrent protection threshold setting can be influenced by the Cold Load Pickup (CLP)and the
Voltage Dependent O
vercurrent (V DepOC) functions, should this functionality be used.
The Overcurrent function selects the threshold setting according to the following diagram:
Start
Does a Voltage Dependent 
co
ndition exist?
End
Yes
No
V
00646
Use the threshold setting 
ca
lculated by the Voltage 
Dependent function
Does a cold Load Pickup 
condition exist?
Yes
Use the current threshold setting 
defined in the COLD LOAD 
PICKUP column
Use the current threshold setting 
de
fined in the OVERCURRENT  
column
No
Figure 41: Selecting the current threshold setting
P14x Chapter 6 - Current Protection Functions
P14xEd1-TM-EN-1 109