EasyManuals Logo

GE MicroVersaTrip Plus User Manual

GE MicroVersaTrip Plus
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #30 background imageLoading...
Page #30 background image
MicroVersaTrip Plus™ and MicroVersaTrip PM™ Trip Units
Chapter 2. Setup Mode
20
Figure 26. Trip Unit display for voltage-unbalance relay pickup.
Voltage-Unbalance Relay Delay
This function sets the delay time before a voltage-
unbalance trip occurs. The range of delays is 1 to 15
seconds, in steps of 1 second. Choosing
OFF disables
voltage-unbalance protection. The Trip Unit display
is shown in Figure 27.
Figure 27. Trip Unit display for voltage-unbalance relay delay.
Current-Unbalance Relay Pickup
This function compares the true RMS current in the
highest or lowest phase with the average of all three
phases and initiates a trip if the difference exceeds
the set point. The range of set points is 10 to 50% of
the unbalance, with an increment of 1%. The Trip
Unit display is shown in Figure 28.
Figure 28. Trip Unit display for current-unbalance relay pickup.
Current-Unbalance Relay Delay
This function sets the delay time before a current-
unbalance trip occurs. The range of delays is 1 to 15
seconds, in steps of 1 second. Choosing
OFF disables
current-unbalance protection. The Trip Unit display
is shown in Figure 29.
Figure 29. Trip Unit display for current-unbalance relay delay.
Undervoltage Relay Pickup
This function measures the true rms voltage in all
phases and initiates a trip if any phase voltage drops
below the set point. The range of set points is 50 to
90% of the nominal voltage, with an increment of
1%. The Trip Unit display is shown in Figure 30.
Figure 30. Trip Unit display for undervoltage relay pickup.
Undervoltage Relay Zero-Volt Trip Enable
This function determines if the relay trips when all
three phase voltages drop to zero volts. The Trip
Unit display for zero-volt trip disabled is shown in
Figure 31. The Trip Unit display for zero-volt trip
enabled is shown in Figure 32.
Figure 31. Trip Unit display for undervoltage relay zero-volt trip
disabled.

Table of Contents

Other manuals for GE MicroVersaTrip Plus

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE MicroVersaTrip Plus and is the answer not in the manual?

GE MicroVersaTrip Plus Specifications

General IconGeneral
BrandGE
ModelMicroVersaTrip Plus
CategoryCircuit breakers
LanguageEnglish

Related product manuals