Section 3
GE POWER/VAC Power Circuit Breaker Characteristics
Symetrical Ratings Basis per ANSI C37.06 - 2000
2400 1200-4000 31.5 5 or 3 31.5 82
4160 1200-4000 40 5 or 3 40 104
4200 1200-4000 50 5 or 3 50 130
1200-4000 63 * 5 63 164
6600 1200-4000 40 5 or 3 40 104
6900 1200-4000 50 * 5 or 3 50 130
7200 1200-4000 63 * 5 63 164
12000 1200-4000 20 5 or 3 20 52
12470 1200-4000 25 5 or 3 25 65
13200 1200-4000 31.5 5 or 3 31.5 82
13800 1200-4000 40 5 or 3 40 104
14400 1200-4000 50 5 or 3 50 130
1200-4000 63 5 63 164
Notes:
1 Maximum voltage for which the breaker is designed and upper limit of operation.
2 Available current ratings are 1200A, 2000A, 3000A, 3500A and 4000A. 4000A rating is forced-air cooled, indoor constrcution only.
3500A is available in outdoor construction, but must be derated to 3250A.
3 At system operating voltages equal to or less than rated maximum voltage.
AVAILABLE RATINGS
4.76
8.25
15
6019
Rated
Permissible
Tripping Delay, Y
(Seconds)
Rated Interrupting
Time (Cycles)
36
2 Sec Short
time Current
Carrying
Capability
(kA)
36
95
95
2
2
2
Typical System
Operating
Voltages (kV)
Peak Close and
Latch
(2.6K x short
circuit current
rating)
(kA)
Rated Maximum
rms Voltage (kV)
(1)
Rated Voltage
Range Factor,
K
Rated Withstand
Test Voltage
Continuous rms
Current Rating at
60Hz (amperes)
(2)
Rated Short
Circuit Current
(Maximum
Interrupting
Capability)
(kA) (3)
Low Frequency
rms Voltage (kV)
Crest Impulse
Voltage (kV)
Nominal ANSI
Voltage Class
(kV)
1.0
1.0
1.0
4.16
7.2
13.8
Table 3-1.1 Power/Vac
®
Power Circuit Breaker Characteristics, K = 1.0
3-3
Notes:
1 Maximum voltage for which the breaker is designed and upper limit of operation.
2 Available current ratings are 1200A, 2000A, 3000A, 3500A and 4000A. 4000A rating is forced-air cooled, indoor construction only.
3500A is available in outdoor construction, but must be derated to 3250A.
3 At system operating voltages equal to or less than rated maximum voltage.
* Ratings offered in addition to the ANSI preferred values
Power/Vac Power
®
Circuit Breaker Characteristics
Symetrical Ratings Basis per ANSI C37.06 - 2000
New Lineup Breakers = 40kA
dd to Service Center Switchgear = 50kA