EasyManuals Logo

GE P54B User Manual

GE P54B
850 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #202 background imageLoading...
Page #202 background image
breaker remains closed after the reclaim timer expires, the Autoreclose cycle is complete, and signals are
generated to indicate that Autor
eclose was successful. These are:
CB1 Succ 1P AR (Single-phase Autoreclose CB1)
CB2 Succ 1P AR (Single-phase Autoreclose CB2)
CB1 Succ 3P AR (Three-phase Autoreclose CB1)
CB2 Succ 3P AR (Three-phase Autoreclose CB2)
These signals increment the relevant circuit breaker successful Autoreclose shot counters, as well as resetting the
Autoreclose in progress signal.
The relevant circuit breaker successful Autoreclose shot counters are:
CB1 SUCC SPAR (Single-phase Autoreclose CB1)
CB1 SUCC 3PAR Shot1 (Three-phase Autoreclose CB1, Shot 1)
CB1 SUCC 3PAR Shot2 (Three-phase Autoreclose CB1, Shot 2)
CB1 SUCC 3PAR Shot3 (Three-phase Autoreclose CB1, Shot 3)
CB1 SUCC 3PAR Shot4 (Three-phase Autoreclose CB1, Shot 4)
CB2 SUCC SPAR (Single-phase Autoreclose CB2)
CB2 SUCC 3PAR Shot1 (Three-phase Autoreclose CB2, Shot 1)
CB2 SUCC 3PAR Shot2 (Three-phase Autoreclose CB2, Shot 2)
CB2 SUCC 3PAR Shot3 (Three-phase Autoreclose CB2, Shot 3)
CB1 SUCC 3PAR Shot4 (Three-phase Autoreclose CB2, Shot 4)
Chapter 7 - Autoreclose P54A/B/C/E
176 P54xMED-TM-EN-1

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE P54B and is the answer not in the manual?

GE P54B Specifications

General IconGeneral
BrandGE
ModelP54B
CategoryRelays
LanguageEnglish

Related product manuals