EasyManuals Logo

GE P54B User Manual

GE P54B
850 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #255 background imageLoading...
Page #255 background image
3.3 APPLICATION NOTES
3.3.1 OVERVOLTAGE SETTING GUIDELINES
The provision of multiple stages and their respective operating characteristics allows for a number of possible
applications:
Definite Time can be used for both stages to pr
ovide the required alarm and trip stages.
Use of the IDMT characteristic allows grading of the time delay according to the severity of the overvoltage.
As the voltage settings for both of the stages are independent, the second stage could then be set lower
than the first to provide a time-delayed alarm stage.
If only one stage of overvoltage protection is required, or if the element is required to provide an alarm only,
the remaining stage may be disabled.
This type of protection must be co-ordinated with any other overvoltage devices at other locations on the system.
P54A/B/C/E Chapter 10 - Voltage Protection Functions
P54xMED-TM-EN-1 229

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE P54B and is the answer not in the manual?

GE P54B Specifications

General IconGeneral
BrandGE
ModelP54B
CategoryRelays
LanguageEnglish

Related product manuals