Power
Break
®
II
Circuit
Breakers
Chapter
1
.
Introduction
4
jl
1
-
3
Preparation
for
Installation
1
-
1
Overview
Power
Break
®
II
insulated
-
case
circuit
breakers
are
designed
to
protect
low
-
voltage
power
circuits
and
equipment
.
They
are
available
with
MicroVersa
-
Trip
®
Plus
and
PM
Trip
Units
for
fault
detection
.
Electrical
Connections
Using
an
industry
-
accepted
solvent
,
remove
any
foreign
material
from
the
line
and
load
strap
sur
-
faces
and
the
corresponding
surfaces
of
the
con
-
necting
bus
.
Ensure
that
the
mating
surfaces
are
smooth
and
free
of
burrs
and
nicks
.
Place
the
bus
connections
in
position
and
align
the
mounting
holes
.
Insert
and
fasten
the
mounting
bolts
and
washers
according
to
specifications
in
Table
2
.
1
-
2
Receiving
the
Breaker
Unpack
the
circuit
breaker
and
inspect
it
for
ship
-
ping
damage
.
Ensure
that
the
breaker
has
the
proper
current
,
voltage
,
and
interruption
ratings
for
the
application
by
comparing
the
catalog
number
with
the
table
in
the
Getting
Started
section
on
the
inside
front
page
.
The
weights
of
the
various
frame
sizes
are
listed
in
Table
1
,
for
reference
.
Bus
Connection
Breaker
Frame
Bolt
Diam
.
Torque
(
in
-
lb
)
(
1
)
1
/
2
in
.
300
800
A
Operation
Type
Frame
Rating
Weight
(
2
)
l
/
2
in
.
1600
-
2000
A
300
(
ib
.
)
Table
2
.
Bolt
sizes
and
mounting
torques
for
bus
connections
.
71
800
A
Manual
Electrical
80
Panel
Cutouts
and
Clearances
Use
the
following
information
to
prepare
the
equipment
and
assure
proper
clearances
for
instal
-
lation
and
operation
of
the
breaker
.
Figure
1
shows
the
front
-
panel
escutcheon
cutout
pattern
and
the
locations
of
the
breaker
mounting
bolts
.
The
standard
door
cutout
dimensions
require
a
trim
plate
on
the
breaker
.
The
optional
dimen
-
sions
are
for
flush
front
or
non
-
hinged
door
con
-
struction
and
the
trim
plate
may
be
omitted
.
Venti
-
lation
cutouts
are
required
for
stationary
-
mounted
1600
A
and
2000
A
frame
breakers
and
for
draw
-
out
-
mounted
2000
A
frame
breakers
.
Ventilation
cutouts
are
not
required
for
drawout
-
mounted
800
A
or
1600
A
frame
breakers
or
for
stationary
-
mounted
800
A
frame
breakers
.
Because
of
arc
chamber
venting
,
the
minimum
through
-
air
distance
from
the
top
of
the
breaker
s
molded
case
to
grounded
metal
is
4
50
inches
[
114
mm
]
in
an
area
5.31
inches
x
16.00
inches
[
135
mm
x
406
mm
]
,
centered
over
the
vent
screens
.
(
Refer
to
outline
drawings
10054370
,
Sheets
1
-
5
,
for
details
.
)
79
2000
A
Manual
Electrical
88
Table
1
.
Weights
of
various
breaker
frame
sizes
,
with
and
without
motor
operator
;
Storage
The
breaker
should
be
placed
in
service
immedi
-
ately
in
its
permanent
location
.
However
,
if
it
must
be
stored
for
an
indefinite
period
,
it
should
be
care
-
fully
protected
against
condensation
,
preferably
by
storage
in
a
warm
dry
room
.
Circuit
breakers
for
outdoor
equipment
should
be
stored
in
that
equip
-
ment
only
when
power
is
available
and
heaters
are
in
operation
,
to
prevent
condensation
.
The
breaker
should
be
stored
in
a
clean
location
,
free
from
corrosive
gases
or
fumes
.
In
particular
,
protect
the
breaker
from
moisture
and
cement
dust
,
as
that
combination
may
be
corrosive
.
If
the
breaker
is
stored
for
any
length
of
time
,
it
should
be
inspected
periodically
to
ensure
good
mechanical
condition
.
i
Courtesy of NationalSwitchgear.com

Other manuals for GE Power Break II

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Power Break II and is the answer not in the manual?

GE Power Break II Specifications

General IconGeneral
BrandGE
ModelPower Break II
CategoryCircuit breakers
LanguageEnglish

Related product manuals