Page 20 Protimeter MMS Moisture Measurement System
A1.2.2 Sub-Surface ERH Test Procedure
(using Protimeter Humidity Sleeves)
Protimeter Humidity Sleeves are convenient optional accessories for use with 
Protimeter Hygrosticks. Clearance holes are drilled at the required POMs and 
the Humidity Sleeves are inserted. As each Humidity Sleeve has its own 
sealing cap, it is not necessary to plug or cover the drilled holes. Having 
placed the Humidity Sleeves in the floor slab (ideally, 24 hours before ERH 
measurements are to be taken), remove the cap and follow the procedure 
starting with step 2 in the previous section. Please refer to local standards such 
as ASTM F2170 (USA) for specific requirements.
A1.2.3 Sub-Surface ERH Test Procedure
(using Protimeter Surface Humidity Box)
If it is impractical or undesirable to take sub-surface ERH readings (the best 
technique for determining the actual moisture condition of the slab) the 
Hygrostick can be used in combination with a Humidity Box placed on the 
surface. Typically, Humidity Boxes are used on floors with embedded heating 
pipes or when a contractor is working to standards, such as BS 8203:1996 
(UK), that specify surface ERH techniques.
A Protimeter Humidity Box (Part No. BLD4711) is available as an optional 
accessory. It should be used in accordance with applicable standard 
recommendations, or it should be placed at the POM for at least 24-hours 
prior to taking ERH readings.
The information contained in this manual is given in good faith. As the method of use of the 
instrument (and its accessories) and the interpretation of the readings are beyond the 
control of the manufacturers, they cannot accept responsibility for any loss, consequential 
or otherwise, resulting from its use.