5-16 T35 Transformer Protection System GE Multilin
5.2 PRODUCT SETUP 5 SETTINGS
5
• In Local Authentication mode, the Observer role does not have a password associated with it. In Remote Authentica-
tion mode the Observer role requires a password.
• The default password is “ChangeMe1#”.
• Once the passwords are set, the Administrator with Supervisor approval can change the role associated password.
• In CyberSentry, password encryption is not supported.
d) SESSION SETTINGS
PATH: SETTINGS PRODUCT SETUP SECURITY SESSION SETTINGS
The following session settings are available.
• SESSION LOCKOUT: This setting specifies the number of failed authentications (the default is three and the maxi-
mum is 99) before the device blocks subsequent authentication attempts for the lockout period. A value of zero means
lockout is disabled.
• SESSION LOCKOUT PERIOD: This setting specifies the period of time in minutes of a lockout period (the default is
three and the maximum is 9999). A value of 0 means that there is no lockout period.
e) RESTORE DEFAULTS
PATH: SETTINGS PRODUCT SETUP SECURITY RESTORE DEFAULTS
• LOAD FACTORY DEFAULTS: This setting is used to reset all the settings, communication and security passwords. An
Administrator role is used to change this setting and a Supervisor role (if not disabled) approves it.
f) SUPERVISORY
PATH: SETTINGS PRODUCT SETUP SECURITY SUPERVISORY
SESSION
SETTINGS
SESSION LOCKOUT:
3
Range: 0 to 99
MESSAGE
SESSION LOCKOUT
PERIOD: 3 min
Range: 0 to 9999 minutes
RESTORE DEFAULTS
LOAD FACTORY
DEFAULTS: No
Range: Yes, No
SUPERVISORY
LOCAL
AUTHENTICATION:Yes
Range: Yes, No
MESSAGE
BYPASS ACCESS:
Disabled
Range: Enabled, Disabled
MESSAGE
LOCK RELAY:
Disabled
Range: Enabled, Disabled
MESSAGE
FACTORY SERVICE:
MODE: Disabled
Range: Enabled, Disabled
MESSAGE
SELF TESTS
See below
MESSAGE
SUPERVISOR ROLE:
Disabled
Range: Enabled, Disabled
MESSAGE
SERIAL INACTIVITY
TIMEOUT: 1 min
Range: 1 to 9999 minutes