EasyManua.ls Logo

GE T35 UR Series

GE T35 UR Series
568 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9-10 T35 Transformer Protection System GE Multilin
9.2 DIFFERENTIAL CHARACTERISTIC TEST EXAMPLES 9 COMMISSIONING
9
9.2.4 TEST EXAMPLE 3
Yg/D30° TRANSFORMER WITH PHASE B TO C FAULT ON THE DELTA SIDE.
Transformer: Y/D30°, 20 MVA, 115/12.47 kv, CT1 (200:1), CT2 (1000:1)
Figure 9–4: CURRENT DISTRIBUTION ON A YG/D30° TRANSFORMER WITH AN a TO b FAULT ON THE LV SIDE
Three adjustable currents are required in this case. The Phase A and C Wye-side line currents, identical in magnitude but
displaced by 180°, can be simulated with one current source passed through these relay terminals in series. The second
current source simulates the Phase B primary current. The third source simulates the delta “b” and “c” phase currents, also
equal in magnitude but displaced by 180°.
TEST PHASE INJECTED CURRENT DISPLAYED CURRENT STATUS
W1 CURRENT W2 CURRENT DIFFERENTIAL RESTRAINT
Balanced
Condition
A 0.25 0 0 0 Not Applicable
B0.5 –180° 0.8 0 0.8
C 0.25 0.8 –180° 0 0.8 –180°
Min Pickup
change the
Min PKP to
0.2 pu
A 0.25 0 0 0 Block
I
d
= 0.051 < Min PKP
B0.5 –180° 0.95 0.154 0.948
C 0.25 0.95 –180° 0.155 0.950 –180°
Minimum
Pickup
A 0.25 0 0 0 Operate
I
d
= 0.102 > Min PKP
B0.5 –180° 1.05 0.253 1.049
C 0.25 1.05 –180° 0.255 1.050 –180°
Slope 1
return the
Min PKP to
0.1 pu
A 0.25 0 0 0 Block
I
d
/I
r
= 13.2%
B0.5 –180° 0.92 0.123 0.919
C 0.25 0.92 –180° 0.123 0.919 –180°
Slope 1 A 0.25 0 0 0 Operate
I
d
/I
r
= 15.9%
B0.5 –180° 0.95 0.153 0.948
C 0.25 0.95 –180° 0.153 0.948 –180°
Intermediate
Slope 1 & 2
A2 0 0 0 Block
I
d
/I
r
= 84.3%
< 86.6%
computed
B4 –180° 1 5.37 –180° 6.37
C2 1 –180° 5.37 6.37 –180°
Intermediate
Slope 1 & 2
A2 0 0 0 Operate
I
d
/I
r
= 87.5%
> 86.6%
computed
B4 –180° 0.8 5.57 180° 6.37
C2 0.8 –180° 5.57 6.37 –180°
Slope 2 A 4 0 0 0 Block
I
d
/I
r
= 93.7%
< Slope 2 = 95%
B8 –180° 0.8 11.93 –180° 12.73
C4 0.8 –180° 11.93 12.73 –180°
Slope 2 A 4 0 0 0 Operate
I
d
/I
r
= 95.7%
> Slope 2 = 95%
B8 –180° 0.6 12.13 –180° 12.73
C4 0.6 –180° 12.13 12.73 –180°
828738A1.CDR
Y/d30° Transformer
F
I (f) = 0.5 pu –270°
A
I (f) = 0.866 pu –90°
b
I(f)=0
a
I (f) = 0.866 pu –270°
c
I (f) = 1 pu –90°
B
I (f) = 0.5 pu –270°
C
A
B
C
A
B
C

Table of Contents

Related product manuals