EasyManua.ls Logo

GE T35 UR Series

GE T35 UR Series
568 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5-160 T35 Transformer Protection System GE Multilin
5.7 CONTROL ELEMENTS 5 SETTINGS
5
CT FAIL 3V0 INPUT PICKUP: This setting specifies the pickup value for the 3V_0 source.
CT FAIL PICKUP DELAY: This setting specifies the pickup delay of the CT failure element.
Figure 5–61: CT FAILURE DETECTOR SCHEME LOGIC
CT FAIL FUNCTION:
CT FAIL BLOCK:
CT FAIL 3IO INPUT1: CT FAIL 3IO INPUT1 PKP:
CT FAIL 3VO INPUT: CT FAIL 3VO INPUT:
CT FAIL 3IO INPUT2: CT FAIL 3IO INPUT2 PKP:
CT FAIL PICKUP DELAY:
AND
OR
SETTING
Enabled=1
Disabled=0
SETTING
SETTING SETTING
SETTING SETTING
SETTING SETTING
SETTING
Off=0
SRC1 RUN 3IO > PICKUP
3IO > PICKUP
3VO > PICKUPSRC1 RUN
SRC2 RUN
FLEXLOGIC OPERANDS
CT FAIL OP
CT FAIL PKP
827048A6.CDR
0

Table of Contents

Related product manuals