B-12 T35 Transformer Protection System GE Multilin
B.4 MEMORY MAPPING APPENDIX B
B
15FB Field Contact Output Physical States (8 items) 0 to 65535 --- 1 F500 0
1603 Field Shared Input States 0 to 65535 --- 1 F500 0
1604 Field Shared Input Channel States 0 to 65535 --- 1 F500 0
1605 Field Shared Input Test States 0 to 65535 --- 1 F500 0
1606 Field Shared Output Operand States 0 to 65535 --- 1 F500 0
1607 Field Latching Output Open Operand States 0 to 65535 --- 1 F500 0
1608 Field Latching Output Close Operand States 0 to 65535 --- 1 F500 0
1609 Field Latching Output Open Driver States 0 to 65535 --- 1 F500 0
160A Field Latching Output Close Driver States 0 to 65535 --- 1 F500 0
160B Field Latching Output Physical States 0 to 65535 --- 1 F500 0
160C Field Unit Online/Offline States 0 to 65535 --- 1 F500 0
160D Field RTD Input Trouble States 0 to 65535 --- 1 F500 0
160E Field Transducer Input Trouble States 0 to 65535 --- 1 F500 0
Ethernet Fibre Channel Status (Read Only)
1610 Ethernet Primary Fibre Channel Status 0 to 2 --- 1 F134 0 (Fail)
1611 Ethernet Secondary Fibre Channel Status 0 to 2 --- 1 F134 0 (Fail)
1612 Ethernet Tertiary Fibre Channel Status 0 to 2 --- 1 F134 0 (Fail)
Data Logger Actuals (Read Only)
1618 Data Logger Channel Count 0 to 16 channel 1 F001 0
1619 Time of Oldest Available Samples 0 to 4294967295 seconds 1 F050 0
161B Time of Newest Available Samples 0 to 4294967295 seconds 1 F050 0
161D Data Logger Duration 0 to 999.9 days 0.1 F001 0
Field Unit RTD Actuals (Read Only) (8 modules)
16C0 Field RTD x Value -32768 to 32767 °C 1 F002 0
16C1 ...Repeated for module number 2
16C2 ...Repeated for module number 3
16C3 ...Repeated for module number 4
16C4 ...Repeated for module number 5
16C5 ...Repeated for module number 6
16C6 ...Repeated for module number 7
16C7 ...Repeated for module number 8
Field Unit Transducer Actuals (Read Only) (8 modules)
16C8 Field Transducer 1 Value -32.768 to 32.767 --- 0.001 F004 0
16CA ...Repeated for Field Transducer 2
16CC ...Repeated for Field Transducer 3
16CE ...Repeated for Field Transducer 4
16D0 ...Repeated for Field Transducer 5
16D2 ...Repeated for Field Transducer 6
16D4 ...Repeated for Field Transducer 7
16D6 ...Repeated for Field Transducer 8
Source Current (Read Only) (6 modules)
1800 Source 1 Phase A Current RMS 0 to 999999.999 A 0.001 F060 0
1802 Source 1 Phase B Current RMS 0 to 999999.999 A 0.001 F060 0
1804 Source 1 Phase C Current RMS 0 to 999999.999 A 0.001 F060 0
1806 Source 1 Neutral Current RMS 0 to 999999.999 A 0.001 F060 0
1808 Source 1 Phase A Current Magnitude 0 to 999999.999 A 0.001 F060 0
180A Source 1 Phase A Current Angle -359.9 to 0 degrees 0.1 F002 0
180B Source 1 Phase B Current Magnitude 0 to 999999.999 A 0.001 F060 0
180D Source 1 Phase B Current Angle -359.9 to 0 degrees 0.1 F002 0
180E Source 1 Phase C Current Magnitude 0 to 999999.999 A 0.001 F060 0
1810 Source 1 Phase C Current Angle -359.9 to 0 degrees 0.1 F002 0
1811 Source 1 Neutral Current Magnitude 0 to 999999.999 A 0.001 F060 0
1813 Source 1 Neutral Current Angle -359.9 to 0 degrees 0.1 F002 0
1814 Source 1 Ground Current RMS 0 to 999999.999 A 0.001 F060 0
Table B–10: MODBUS MEMORY MAP (Sheet 4 of 52)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT