B-18 T35 Transformer Protection System GE Multilin
B.4 MEMORY MAPPING APPENDIX B
B
3332 Supervisor Role Enable 0 to 1 --- 1 F102 0 (Disabled)
3333 Lock Relay 0 to 1 --- 1 F102 0 (Disabled)
3334 Factory Service Mode Enable 0 to 1 --- 1 F102 0 (Disabled)
3335 Failed Authentication Alarm Enable 0 to 1 --- 1 F102 1 (Enabled)
3336 Firmware Lock Alarm 0 to 1 --- 1 F102 1 (Enabled)
3337 Settings Lock Alarm 0 to 1 --- 1 F102 1 (Enabled)
3338 Bypass Access 0 to 1 --- 1 F102 0 (Disabled)
3339 Encryption 0 to 1 --- 1 F102 1 (Enabled)
333A Serial Inactivity Timeout 1 to 9999 min 1 F001 1
Security Command (Read/Write Command)
3350 Operator Logoff 0 to 1 --- 1 F126 0 (No)
3351 Engineer Logoff 0 to 1 --- 1 F126 0 (No)
3352 Administrator Logoff 0 to 1 --- 1 F126 0 (No)
3353 Clear Security Data 0 to 1 --- 1 F126 0 (No)
Security Reserved Modbus Registers (Read/Write)
3360 Address 0x3360 reserved for serial login (20 items) 0 to 9999 --- 1 F001 3
3374 Address 0x3374 reserved for serial logout 0 to 9999 --- 1 F001 3
Security Reserved Modbus Registers (Read Only)
3375 Address 0x3374 reserved for serial logout 0 to 5 --- 1 F617 3 (Engineer)
Event Recorder (Read Only)
3400 Events Since Last Clear 0 to 4294967295 --- 1 F003 0
3402 Number of Available Events 0 to 4294967295 --- 1 F003 0
3404 Event Recorder Last Cleared Date 0 to 4294967295 --- 1 F050 0
Event Recorder Commands (Read/Write Command)
3406 Event Recorder Clear Command 0 to 1 --- 1 F126 0 (No)
DCmA Input Values (Read Only) (24 modules)
34C0 DCmA Inputs 1 Value -9999.999 to 9999.999 --- 0.001 F004 0
34C2 DCmA Inputs 2 Value -9999.999 to 9999.999 --- 0.001 F004 0
34C4 DCmA Inputs 3 Value -9999.999 to 9999.999 --- 0.001 F004 0
34C6 DCmA Inputs 4 Value -9999.999 to 9999.999 --- 0.001 F004 0
34C8 DCmA Inputs 5 Value -9999.999 to 9999.999 --- 0.001 F004 0
34CA DCmA Inputs 6 Value -9999.999 to 9999.999 --- 0.001 F004 0
34CC DCmA Inputs 7 Value -9999.999 to 9999.999 --- 0.001 F004 0
34CE DCmA Inputs 8 Value -9999.999 to 9999.999 --- 0.001 F004 0
34D0 DCmA Inputs 9 Value -9999.999 to 9999.999 --- 0.001 F004 0
34D2 DCmA Inputs 10 Value -9999.999 to 9999.999 --- 0.001 F004 0
34D4 DCmA Inputs 11 Value -9999.999 to 9999.999 --- 0.001 F004 0
34D6 DCmA Inputs 12 Value -9999.999 to 9999.999 --- 0.001 F004 0
34D8 DCmA Inputs 13 Value -9999.999 to 9999.999 --- 0.001 F004 0
34DA DCmA Inputs 14 Value -9999.999 to 9999.999 --- 0.001 F004 0
34DC DCmA Inputs 15 Value -9999.999 to 9999.999 --- 0.001 F004 0
34DE DCmA Inputs 16 Value -9999.999 to 9999.999 --- 0.001 F004 0
34E0 DCmA Inputs 17 Value -9999.999 to 9999.999 --- 0.001 F004 0
34E2 DCmA Inputs 18 Value -9999.999 to 9999.999 --- 0.001 F004 0
34E4 DCmA Inputs 19 Value -9999.999 to 9999.999 --- 0.001 F004 0
34E6 DCmA Inputs 20 Value -9999.999 to 9999.999 --- 0.001 F004 0
34E8 DCmA Inputs 21 Value -9999.999 to 9999.999 --- 0.001 F004 0
34EA DCmA Inputs 22 Value -9999.999 to 9999.999 --- 0.001 F004 0
34EC DCmA Inputs 23 Value -9999.999 to 9999.999 --- 0.001 F004 0
34EE DCmA Inputs 24 Value -9999.999 to 9999.999 --- 0.001 F004 0
RTD Input Values (Read Only) (48 modules)
34F0 RTD Input 1 Value -32768 to 32767 °C 1 F002 0
34F1 RTD Input 2 Value -32768 to 32767 °C 1 F002 0
34F2 RTD Input 3 Value -32768 to 32767 °C 1 F002 0
Table B–10: MODBUS MEMORY MAP (Sheet 10 of 52)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT

Table of Contents