B-34 T35 Transformer Protection System GE Multilin
B.4 MEMORY MAPPING APPENDIX B
B
5D07 Ground Time Overcurrent 1 Block 0 to 4294967295 --- 1 F300 0
5D09 Ground Time Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
5D0A Ground Time Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)
5D0B Reserved (6 items) 0 to 1 --- 1 F001 0
5D11 ...Repeated for Ground Time Overcurrent 2
5D22 ...Repeated for Ground Time Overcurrent 3
5D33 ...Repeated for Ground Time Overcurrent 4
5D44 ...Repeated for Ground Time Overcurrent 5
5D55 ...Repeated for Ground Time Overcurrent 6
CT Fail (Read/Write Setting) (6 modules)
5E6C CT Fail 1 Function 0 to 1 --- 1 F102 0 (Disabled)
5E6D CT Fail 1 Block 0 to 4294967295 --- 1 F300 0
5E6F CT Fail 1 Current Source 1 0 to 5 --- 1 F167 0 (SRC 1)
5E70 CT Fail 1 Current Pickup 1 0 to 2 pu 0.1 F001 2
5E71 CT Fail 1 Current Source 2 0 to 5 --- 1 F167 1 (SRC 2)
5E72 CT Fail 1 Current Pickup 2 0 to 2 pu 0.1 F001 2
5E73 CT Fail 1 Voltage Source 0 to 5 --- 1 F167 0 (SRC 1)
5E74 CT Fail 1 Voltage Pickup 0 to 2 pu 0.01 F001 20
5E75 CT Fail 1 Pickup Delay 0 to 65.535 s 0.001 F001 1000
5E76 CT Fail 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
5E77 CT Fail 1 Events 0 to 1 --- 1 F102 0 (Disabled)
5E78 ...Repeated for CT Fail 2
5E84 ...Repeated for CT Fail 3
5E90 ...Repeated for CT Fail 4
5E9C ...Repeated for CT Fail 5
5EA8 ...Repeated for CT Fail 6
Setting Groups (Read/Write Setting)
5F70 Setting Group for Modbus Comms (0 means group 1) 0 to 5 --- 1 F001 0
5F71 Setting Groups Block 0 to 4294967295 --- 1 F300 0
5F73 FlexLogic Operands to Activate Groups 2 through 6 (5
items)
0 to 4294967295 --- 1 F300 0
5F7D Setting Group Function 0 to 1 --- 1 F102 0 (Disabled)
5F7E Setting Group Events 0 to 1 --- 1 F102 0 (Disabled)
Setting Groups (Read Only)
5F7F Current Setting Group 0 to 5 --- 1 F001 0
Setting Group Names (Read/Write Setting)
5F8C Setting Group 1 Name --- --- --- F203 (none)
5F94 Setting Group 2 Name --- --- --- F203 (none)
5F9C Setting Group 3 Name --- --- --- F203 (none)
5FA4 Setting Group 4 Name --- --- --- F203 (none)
5FAC Setting Group 5 Name --- --- --- F203 (none)
5FB4 Setting Group 6 Name --- --- --- F203 (none)
Transformer Percent Differential (Read/Write Grouped Setting)
61C0 Percent Differential Function 0 to 1 --- 1 F102 0 (Disabled)
61C1 Percent Differential Pickup 0.05 to 1 pu 0.001 F001 100
61C2 Percent Differential Slope 1 15 to 100 % 1 F001 25
61C3 Percent Differential Break 1 1 to 2 pu 0.001 F001 2000
61C4 Percent Differential Break 2 2 to 30 pu 0.001 F001 8000
61C5 Percent Differential Slope 2 50 to 100 % 1 F001 100
61C6 Inrush Inhibit Function 0 to 2 --- 1 F168 1 (Adapt. 2nd)
61C7 Inrush Inhibit Level 1 to 40 %fo 0.1 F001 200
61C8 Overexcitation Inhibit Function 0 to 1 --- 1 F169 0 (Disabled)
61C9 Overexcitation Inhibit Level 1 to 40 %fo 0.1 F001 100
61CA Percent Differential Block 0 to 4294967295 --- 1 F300 0
Table B–10: MODBUS MEMORY MAP (Sheet 26 of 52)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT