CHAPTER 5: SETTINGS PRODUCT SETUP
T35 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-67
5
Figure 5-27: IEC 61850 TxGOOSE panel
A data set needs to be set up and selected in the TxGOOSEx DatSet field for all content to display.
When saving changes, when a "dataset member is empty" message displays, you need to set the member in the bottom 
right of the window.
TxGOOSE1 MODE
Range: Disabled, GOOSE, R-GOOSE
Default: Disabled
When set to Disabled, TxGOOSE1 messages are not published. When set to GOOSE, TxGOOSE1 messages are published 
in IEC 61850 8 1:2011 GOOSE format. When set to R-GOOSE, TxGOOSE1 messages are published in Routable GOOSE 
format according to IEC 61850 90-5, and the 
TxGOOSE1 DST MAC address is set to 00 00 00 00 00 00 and cannot be 
changed.
TxGOOSE1 GoCB name
Range: 0 up to 32 VisibleString characters
Default: GoCB01
The entered value sets the GOOSE control block (GoCB) name value for TxGOOSE1.
An ObjectReference to the control block, which consists of the concatenation of the string "<LDName>/LLN0." and the 
control block name, is published in the gocbRef field of TxGOOSE1 messages and is used by subscribers to discriminate 
TxGOOSE1 messages from other GOOSE messages. <LDName> is a syntactic variable that is set to the value of setting 
Master functional ldName if one or more characters have been entered to that setting, otherwise the value of setting IED 
NAME suffixed with "Master".
TxGOOSE1 GoID
Range: 0 to 129 VisibleString characters
Default: TxGOOSE1
The entered value sets the goID value published in TxGOOSE1 messages, and can be used by subscribers to discriminate 
the TxGOOSE1 messages from other GOOSE messages.