EasyManua.ls Logo

GE T35 - Test Example 3

GE T35
610 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8-10 T35 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
DIFFERENTIAL CHARACTERISTIC TEST EXAMPLES CHAPTER 8: COMMISSIONING
8
8.2.4 Test example 3
8.2.4.1 Yg/D30° transformer with phase B to C fault on the Delta side
Transformer data — Y/D30°, 20 MVA, 115/12.47 kv, CT1 (200:1), CT2 (1000:1)
Figure 8-4: Current Distribution on a Yg/D30° transformer with an a to b fault on the LV side
Three adjustable currents are required in this case. The Phase A and C Wye-side line currents, identical in magnitude but
displaced by 180°, can be simulated with one current source passed through these relay terminals in series. The second
current source simulates the Phase B primary current. The third source simulates the delta “b” and “c” phase currents, also
equal in magnitude but displaced by 180°.
Slope 1 A 0.4435 1.6 –180° 0.110 0.9026 180° Block
I
d
/I
r
= 11.9%
B0 0 0 0
C 0.4435 –180° 0 0 0
Slope 1 A 0.4425 1.7 –180° 0.165 0.979 –180° Operate
I
d
/I
r
= 16.8%
B0 0 0 0
C 0.4425 –180° 0 0.165 0.979
Intermediate
Slope 1 & 2
A1.2 5 –180° 0.675 –180° 2.882 –180° Block
I
d
/I
r
= 23.4%
B0 0 0 0
C1.2 –180° 0 0.675 2.882
Intermediate
Slope 1 & 2
A1.1 5 –180° 0.860 –180° 2.882 –180° Operate
I
d
/I
r
= 29.8%
B0 0 0 0
C1.1 –180° 0 0.860 2.882
Slope 2 A 0.4 15 –180° 7.915 –180° 8.646 –180° Block
I
d
/I
r
= 91.5%
B0 0 0 0
C0.4 –180° 0 7.915 8.646
Slope 2 A 0.2 15 –180° 7.918 –180° 8.650 –180° Operate
I
d
/I
r
= 95.7%
B0 0 0 0
C0.2 –180° 0 7.916 8.650
Test Phase Injected current Displayed current Status
W1 current W2 current Differential Restraint

Table of Contents

Related product manuals