Figure 5-29: RxGOOSE Boolean panel
Most of the settings are configured by drag-and-drop. However the ID, DEFAULT STATE, and EVENTS settings must be 
individually entered when the factory default values are not acceptable.
RxGOOSE Boolean1 ID
Range: 0 to 20 characters
Default: RxG Bool1
This setting allows the user to assign descriptive text to the name of the RxGOOSE Boolean1 FlexLogic operand. The full 
operand name is the value of this setting appended with " On". The standard and enhanced front panels display the first 
17 characters of this setting plus " On" to fit the 20 character display.
RxGOOSE Boolean1 RxGOOSE
Range: None, RxGOOSE1, RxGOOSE2, and so on
Default: None
This setting selects the RxGOOSE containing the value that drives the RxGOOSE Boolean1 FlexLogic operand. If set to 
None, the RxGOOSE Boolean1 FlexLogic operand assumes its default state.
RxGOOSE Boolean1 Member
Range: 1 to 64 in steps of 1
Default: 1
This setting selects the GOOSE message member that drives the RxGOOSE Boolean1 FlexLogic operand. A setting of 1 
selects the first member, 2 selects the second member, and so on. Entering a number greater than the number of 
members in the message and entering the number of a member which does not contain a BOOLEAN results in the 
RxGOOSE Boolean1 FlexLogic operand assuming its default state. The Subscribed to column identifies the particular 
Boolean subscribed to even if the member is a structure containing more than one Boolean.
RxGOOSE Boolean1 DEFAULT STATE
Range: On, Off, Latest/On, Latest/Off
Default: Off
This setting selects the logic state for the RxGOOSE Boolean1 FlexLogic operand if the UR has just completed startup and 
the selected RxGOOSE has not yet received a message, or the selected RxGOOSE has lost its connectivity with the 
publisher. The following choices are available: