CHAPTER 5: SETTINGS FLEXLOGIC
T35 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-183
5
ELEMENT:
Hottest-spot
temperature
XFMR HST-SPOT °C PKP
XFMR HST-SPOT °C OP
XFMR HST-SPOT °C DPO
The hottest-spot temperature element has picked up
The hottest-spot temperature element has operated
The hottest-spot temperature element has dropped out
ELEMENT:
Transformer loss of
life
XFMR LIFE LOST PKP
XFMR LIFE LOST OP
The transformer loss of life element has picked up
The transformer loss of life element has operated
ELEMENT:
Transformer percent
differential
XFMR PCNT DIFF PKP A
XFMR PCNT DIFF PKP B
XFMR PCNT DIFF PKP C
XFMR PCNT DIFF 2ND A
XFMR PCNT DIFF 2ND B
XFMR PCNT DIFF 2ND C
XFMR PCNT DIFF 5TH A
XFMR PCNT DIFF 5TH B
XFMR PCNT DIFF 5TH C
XFMR PCNT DIFF OP
XFMR PCNT DIFF OP A
XFMR PCNT DIFF OP B
XFMR PCNT DIFF OP C
XFMR PCNT DIFF SAT A
XFMR PCNT DIFF SAT B
XFMR PCNT DIFF SAT C
XFMR PCNT DIFF DIR A
XFMR PCNT DIFF DIR B
XFMR PCNT DIFF DIR C
XFMR PCNT DIFF WARN
Transformer percent differential protection has picked up in phase A
Transformer percent differential protection has picked up in phase B
Transformer percent differential protection has picked up in phase C
The 2nd harmonic of transformer percent differential has blocked phase A
The 2nd harmonic of transformer percent differential has blocked phase B
The 2nd harmonic of transformer percent differential has blocked phase C
The 5th harmonic of transformer percent differential has blocked phase A
The 5th harmonic of transformer percent differential has blocked phase B
The 5th harmonic of transformer percent differential has blocked phase C
At least one phase of transformer percent differential has operated
Phase A of transformer percent differential has operated
Phase B of transformer percent differential has operated
Phase C of transformer percent differential has operated
Transformer percent differential SAT flag has triggered on phase A
Transformer percent differential SAT flag has triggered on phase B
Transformer percent differential SAT flag has triggered on phase C
Transformer percent differential DIR flag has triggered on phase A
Transformer percent differential DIR flag has triggered on phase B
Transformer percent differential DIR flag has triggered on phase C
Transformer percent differential current has exceeded 0.5xPKP for 10s
FIXED OPERANDS Off Logic = 0. Does nothing and can be used as a delimiter in an equation list;
used as ‘Disable’ by other features.
On Logic = 1. Can be used as a test setting.
INPUTS/OUTPUTS:
Contact inputs
Cont Ip 1 On
Cont Ip 2 On
Cont Ip 1 Off
Cont Ip 2 Off
Cont Ip 120 On
Cont Ip 120 Off
(does not appear unless ordered)
(does not appear unless ordered)
(does not appear unless ordered)
(does not appear unless ordered)
(does not appear unless ordered)
(does not appear unless ordered)
INPUTS/OUTPUTS:
Contact outputs,
current
(from detector on
form-A output only)
Cont Op 1 IOn
Cont Op 2 IOn
Cont Op 72 IOn
(does not appear unless ordered)
(does not appear unless ordered)
(does not appear unless ordered)
INPUTS/OUTPUTS:
Contact outputs,
voltage
(from detector on
form-A output only)
Cont Op 1 VOn
Cont Op 2 VOn
Cont Op 72 VOn
(does not appear unless ordered)
(does not appear unless ordered)
(does not appear unless ordered)
Cont Op 1 VOff
Cont Op 2 VOff
Cont Op 72 VOff
(does not appear unless ordered)
(does not appear unless ordered)
(does not appear unless ordered)
INPUTS/OUTPUTS:
Direct inputs
DIRECT INPUT 1 On
DIRECT INPUT 32 On
Flag is set, logic=1
Flag is set, logic=1
INPUTS/OUTPUTS:
RxGOOSE DPS
RxG DPS 1 BAD
RxG DPS 1 INTERM
RxG DPS 1 OFF
RxG DPS 1 ON
Asserted while the RxGOOSE double-point status input is in the bad state
Asserted while the RxGOOSE double-point status input is in the intermediate
state
Asserted while the RxGOOSE double-point status input is off
Asserted while the RxGOOSE double-point status input is on
RxG DPS 2 to 5 Same set of operands as per RxG DPS 1
INPUTS/OUTPUTS:
RxGOOSE Booleans
RxG Bool 1 On
RxG Bool 2 On
RxG Bool 3 On
RxG Bool 256 On
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Operand type Operand syntax Operand description