Loading...
7-38 VersaMax Modules, Power Supplies and Carriers User's Manual GFK-1504N
7
IC200MDL635
Input Module, 48 V DC Pos/Neg Logic Grouped 16 Points
Field Wiring
Terminal
Connection
Terminal
Connection
A1
Input 1
B1
No connection
A2
Input 2
B2
No connection
A3
Input 3
B3
No connection
A4
Input 4
B4
No connection
A5
Input 5
B5
No connection
A6
Input 6
B6
No connection
A7
Input 7
B7
No connection
A8
Input 8
B8
No connection
A9
Input 9
B9
No connection
A10
Input 10
B10
No connection
A11
Input 11
B11
No connection
A12
Input 12
B12
No connection
A13
Input 13
B13
No connection
A14
Input 14
B14
No connection
A15
Input 15
B15
No connection
A16
Input 16
B16
No connection
A17
Inputs 1-8 Common
B17
No connection
A18
Inputs 9-16 Common
B18
No connection
The 16 inputs form two groups of 8. Each group has a common connection.
Each group may be wired for positive or negative logic inputs. If additional
bussed terminals are needed, the B terminals can be made available using a
shorting bar. The shorting bar has a maximum current-carrying capacity of 2
Amps per point. Refer to chapter 2 for additional information about using the
shorting bar.
Wiring Connections
for Carriers with Two
Rows of Terminals
IC200CHS002, 005
IC200CHS012, 015
1
2
3
4
5
6
7
8
9
11
12
13
14
15
16
17
18
10
I1
I2
I3
I4
I5
I6
I7
I8
I9
I10
11
I12
I13
I14
I15
I16
A
+
-
(+)
(-)
+
-
(+)
(-)
-
(+)
-
(+)
Wiring Connections
for Carriers with
Three Rows of
Terminals
IC200CHS001, 022, 025
IC200CHS011
A
1
2
3
4
5
6
13
14
15
16
17
18
7
8
9
11
12
10
I1
I2
I3
I4
I5
I6
I7
I8
I9
I10
I11
I12
I16
+
-
(+)
(-)
I13
I14
I15
+
-
(+)
(-)

Table of Contents