IC200MDL730
Output Module, 24 V DC Positive Logic 2.0 A, w/ESCP 8 Points
Module Specifications
Module Characteristics
User input to logic (optical)
and to frame ground
Group to group
250 V AC continuous; 1500 V AC for 1 minute
Not applicable
One green LED per point shows individual point on/off state
One amber LED per point shows individual point overloads/short
circuits.
FLD PWR LED indicates field power is present
OK LED indicates backplane power is present
Backplane current
5 V output: 50mA
+18 to +30 V DC, +24 V DC nominal
Compatibility
Cimplicity
Versa
Control
CPU
CPU
CPU
CPU
DBI
EBI
GBI
PBI
HW,FW vers.
2.11 1.0 2.2
+17.5 to +30 V DC, +24 V DC nominal
Load current 2.0A at 30 V DC maximum (resistive) per point, 8.0A max per
On response time
Off response time
0.5ms, maximum
0.5ms, maximum
Short circuit protection, overcurrent protection
External Power Supply Requirements
The external power supply used to power the loads must provide sufficient field
power for the module during short circuit events. When a load is shorted, an
inadequate external power supply may allow field power to drop below the
specified operating range, causing mis-operation of the module. The external
power supply must be capable of providing short circuit energy without
degradation of output voltage levels. The amount of energy required depends
on the number of simultaneously-shorted points that might occur. Refer to
power supply short circuit operation specifications when selecting the power
supply to be used with the loads. Local energy storage (either batteries or
capacitors) can be used to compensate for insufficient power supply