11-14 VersaMax Modules, Power Supplies and Carriers User's Manual GFK-1504N
11
IC200ALG321
Analog Output Module, 12 Bit Voltage 0 to 10 V DC 4 Channels
Scaling
The following graphs illustrate the relationship between the output voltage
measured at the field terminals and the data that is output by the module.
Count vs Output Voltage
0 3200 6400 9600 12800 16000 19200 22400 25600 28800 32000
Voltage can be calculated using the following equation:
V
out
= ((analog counts x 10.25) / 32768 )
The count value must be a multiple of 8. If the module receives a count value
that is not a multiple of 8, it rounds the value down to the closest multiple of 8.
For example:
Count Voltage