3-14 VersaMax Modules, Power Supplies and CarriersUser's Manual GFK-1504N
3
IC200PWR102
120/240 V AC Expanded 3.3 V Power Supply
Specifications
Input Voltage 85 to 132 V AC with jumper installed, 120 V AC nominal
176 to 264 V AC w/o jumper installed, 240 V AC nominal
Input Power
27VA
Frequency
47 to 63Hz
Holdup Time
20ms
Output Voltage
5 V DC, 3.3 V DC
Protection
Short circuit, overload
Output Current
Total
3.3 V DC Output
5 V DC Output
1.5 A maximum
1.0A maximum
(1.5 A - I
3.3 V
) maximum
The total output current should not exceed 1.5 A. For example, if 3.3 V
at 1.0 A is required, 0.5 A is available on the 5 V output.
Jumper Selection of 120 V AC or 240 V AC
This power supply can be used with either 120 V AC or 240 V AC nominal input
power. For 120 V AC nominal operation, a jumper should be installed as
marked on the power supply.
JUMPER
FOR 120V
The power supply operates without a jumper installed; however, the hold-up
specification is not met. If a jumper is not installed for 120 V AC operation, the
power supply will not cause hazardous conditions.
DO NOT USE A JUMPER FOR 240 V AC OPERATION. If a jumper is used
on the input connector for 240 V AC nominal operation, the power supply
will be damaged and may cause hazardous conditions.
WARNING:

Table of Contents