6.4 Pipes
Pipesandsystemcomponentsmustbecleananddryinsideandfreeofscale,swarfandlayersof
rustandphosphate.Onlyuseair-tightparts.
Lay pipes correctly.Suitable vibration compensators must beprovided to prevent pipesbeing
crackedandbrokenbyseverevibrations.
Ensureaproperoilreturn.
Keeppressurelossestoanabsoluteminimum.
The pipe connectionshavegraduatedinsidediameterssothatpipeswith
standartmillimetreandinchdimensionscanbeused.
Theconnectiondiametersoftheshut-offvalvesareratedformaximum
compressoroutput.Theactualrequiredpipecrosssectionmustbe
matchedtotheoutput.Thesameappliesfornon-returnvalves.
Fig.5:graduated
internaldiameter
6.3 Pipeconnections
ATTENTION Damagepossible.
Superheatingcandamagethevalve.
Removethepipesupportsfromthevalveforsoldering.
Onlysolderusinginertgastoinhibitoxidationproducts(scale).
6 | Compressor assembly
6.5 Layingsuctionandpressurelines
ATTENTION Improperlyinstalledpipescancausecracksandtears,theresult
beingalossofrefrigerant.
INFO Proper layout of the suction and discharge lines directly after
the compressor is integral to the system’s smooth running and
vibrationbehaviour.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GEA Bock HGX44e/475-4 and is the answer not in the manual?

GEA Bock HGX44e/475-4 Specifications

General IconGeneral
BrandGEA
ModelBock HGX44e/475-4
CategoryAir Compressor
LanguageEnglish

Related product manuals