7 | Electrical connection
7.11OilsumpheateratHCandLGcompressors
As the solubility of hydrocarbons and HFO refrigerants in oil can be very high, especially at high
suction pressures, the compressor must be equipped with an oil sump heater.For this reason, a
pump-downcircuitisrecommendedduringstandstilltoreducethesuction-sidestandstillpressures.
ATTENTION Theoilsumpheatermustgenerallybeconnectedandoperated!
•InaTT-orTNsystem,aresidualcurrentprotectiondevice(RCD)
mustbeused.
•
InanITsystem,aninsulationmonitoringdevicemustbeused.
Nationalstandardsandregulationsmustbeobserved.
Compressor Electricaldata
HG44e...HC,HG44e...LG
HG56e...HC,HG56e...LG
230V-1-50/60Hz,160W
7.10Capacityregulator(Accessories)
ATTENTION Afuse(max.3xlBinaccordancewithIEC60127-2-1)corresponding
to the rated current must be placed in front of every magnetic
coilofthecapacityregulatorasshort-circuitprotection.Thera-
tedvoltageofthefusemustbeequaltoorgreaterthantherated
voltageofthemagneticcoil.Theabilityofthefusestoswitchoff
mustbegreaterthanorequaltothemaximumassumableshort-
circuitcurrentattheinstallationlocation.
Capacity regulator DCR14 is not approved for digital capacity
regulationforHCandLGcompressors.