36
D
GB
F
E
96416-08.2020-DGbFEIRu
Type
No.ofcylinders
Displacement
(1450/1740rpm)
Electricaldata
Weight
Connections
Oilcharge
(exworks)
Oilcharge
(sightglasscentre)
Voltage
Max.
operating
current
Max.power
consumption
Starting
current
(rotorlocked)
Dischargeline
DV
Suctionline
SV
50/60Hz PW1+2 PW1/PW1+2
m
3
/h V A kW A kg mm(inch) mm(inch) ltr ltr
HG56e/850-4
6
73.8/88.6
380-420VY/YY-3-50HzPW
440-480VY/YY-3-60HzPW
PW=PartWinding
Windingratio:50%/50%
33 19.7 101/174 194
35(1
3
/
8
) 54(2
1
/
8
) 3.3 2.7
HG56e/850-4S 73.8/88.6 39 23.5 125/209 211
HG56e/995-4
86.6/103.9
39 23.2 125/209 208
HG56e/995-4S
86.6/103.9
46 27.7 149/246 211
HG56e/1155-4
100.4/120.5
47 28.0 149/246 212
HG56e/1155-4S
100.4/120.5
58 33.3 196/335 221
11 | Technical data
1
2
3
2
4
Tolerance(±10%)relativetothemeanvalueofthevoltagerange.
Othervoltagesandtypesofcurrentonrequest.
-Thespecicationsformax.powerconsumptionapplyfor50Hzoperation.
For60Hzoperation,thespecicationshavetobemultipliedbythefactor1.2.
Themax.workingcurrentremainsunchanged.
- Takeaccountofthemax.operatingcurrent/max.powerconsumptionfor
designoffuses,supplylinesandsafetydevices.
Fuse:ConsumptioncategoryAC3
1
2
Allspecicationsarebasedontheaverageofthevoltagerange
Forsolderconnections
3
4
*ThetechnicaldatafortheHCandLGcompressorsareidenticaltothestandardcompressors.Therefore,thesedesignationsarenotincludedinthecompressortypespecication.