EasyManua.ls Logo

GEA Grasso V 1100T - Check list periodical inspection

GEA Grasso V 1100T
62 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2.2.1 Check list periodical inspection
Check list periodical inspection
CHECK POINTS *
5
FREQUENCY REMARKS
daily
weekly
monthly
Oil level in crankcase
Between 25% and 75% height of the sight
glass. For topping up oil, refer to
Section 2.4.1, Page 33.
Colour of the oil
The oil should be transparently clear. A
disappearing white colour points to
dissolved refrigerant.
Lubricating oil pressure
difference
Min. control oil pressure
Oil temperature max.
Refer to the "Product Information"
Oil leakage of shaft seal
max.
In case of more than 1 cc/hr contact
supplier.
Suction pressure
Check against design conditions. Refer to
plant manual.
Discharge pressure
Refer to plant manual. For the max.
allowable discharge pressure refer to the
technical data of compressor.
Suction superheat
Intermediate superheat
≥0 K (NH
3
)
Discharge temperature
max.
170 °C.
Oil temperature min.
During compressor standstill the lower part
of the crankcase must remain warmer than
the surroundings: ≥ 20 °C (NH
3
)
Condition of V-belts
Check belts for:
1) Wear (fraying, cuts etc.) and ensure that
they do not touch the groove bottom.
2) Tension. Too low a tension gives rise to
excessive flapping or oscillation in
operation. For correct tension consult
Grasso instruction 0087516
Adjustment and
operation of pressure
safety switches
Refer also to instructions of switch
manufacturer.
Capacity control (if
provided)
Switching frequency of
the compressor
Number of operating
hours
Check the number of operating hours in
view of any maintenance operations to be
carried out.
2.3 STEPS FOR LONGER SHUT-DOWN PERIODS (> 6 months)
5 During the first 50 operating hours the compressor should be checked regularly for all the points
mentioned above, at least twice every 24 hours and more frequently in cases where irregularities are
found.
INSPECTION AND TROUBLE SHOOTING