Service and maintenance schedules Grasso V 300 .. 1800 (T), excl. GMM
Item
Description
Actions
Checkpoint
Running hours * 1000
10
0.1
Yearly
3 6 - - -
9 - 12 - -
15 - 18 -
21 - - 24 - -
27 30 - - -
33 - - - 36
40
IC/M
E
IC/M
E
IC/M
E
IC/M
E
IC/M
E
IC/M
E
IC/M
E
IC/M
E
Intermediate
cooler and
injection valve
41 CL CL - CL CL CL CL CL
Oil separator
refreshing oil and
cleaning/testing
of float valve
42 - IC IC IC IC RE IC IC
Heavy duty thrust
bearing
43 CL CL CL CL CL CL CL CL
Oil cooler, air
side
44 RE RE - RE RE RE RE RE
Oil cooler, oil
side, refrigeration
oil
45 Refer to specifications of motor manufacturer
Oil cooler, electic
motor (fan)
46 ME
ME/C
L
ME/C
L
ME/C
L
ME/C
L
ME/C
L
ME/C
L
ME/C
L
Cylinder head
water cooling
system
10 Check after every maintenance job the settings and working of all safety devices, regulators and the
running conditions according to the Service Instruction Manual (SIM)
12 A running-in suction gas filter is factory mounted. This running-in filter has to be replaced after max. 100
running hours by a permanent filter. One permanent filter is supplied together with the compressor
MAINTENANCE
0089288gbr_11
30.10.2017 49

Table of Contents