Table 2: Significance of parameters
Parameter description Min Max step factory
setting
c0 how often defrosting will take place
00 – there will be no automatic defrosting, only manual defrosting!!!
-01 there will be no automatic or manual defrosting!!!
-01 24 1h 6h
c1 Maximal time of defrosting, if the evaporator does not reach set
temperature (parameter d2) Note!!! If this parameter is set as ‘-01’
there will be no time limits
-01 99 1min 30min
c2 minimal time of compressor stoppage 0 15 1min 3min
c3 time of evaporator dripping 0 15 1min 2min
c5 Maximal time of operation of compressor
0 – no testing (this parameter is off)
0 99 1min 40min
c6 Time of compressor stoppage after switching on of protection from
parameter ‘c5’
0 99 1min 10min
c7 Time during which after the end of defrosting (parameter ‘c4’)
temperature measured just before the beginning of defrosting will be
displayed
0 60 1min 5min
c8 Compressor operation time with damage of control sensor 1 99 1min 25min
c9 Compressor stoppage time with damage of control sensor 1 60 1min 5min
d0 Minimal temperature for a client to set -40 20 1°C 1°C
d1 Maximal temperature for a client to set d0+1 40 1°C 10°C
d2 Evaporator temperature at which defrosting will stop 0 40 1°C 5°C
d3 Value of hysteresis 1 10 1°C 2°C
d4 Value of rescaling of chamber sensor in comparison with actually
measured temperature
-10 10 1°C 0°C
d6 Temperature in the chamber whose exceeding makes alarm A4
switch on.
only software version 02
-40 40 1°C 40°C
r0 Type of temperature sensor:
00 – NTC 2,2k
01 – NTC 10k
only software version 02
00 01 1 00
r1 Unit connected to other transformer:
00 – lighting
01 – ventilator operating with compressor
02 – ventilator operating all the time
03 – evaporator heater
04 – tray heater
and from software version 02
05 – valve
06 – compressor transformer with more power - ! equipment
replacement required ! ref. to G-201-P00K0x-MH0000
00 04 1 00
r5 Conditions of switching on of defrosting when the unit is switched
on:
00 – beginning of operation without defrosting
01 – if during defrosting power supply is disconnected, defrosting
will be switched on
02 – defrosting after every switching on of unit power supply
00 02 1 00