SCCB TYPE G-202-P00 Service Manual for Producers Page 15
PPUH „GECO” EDITION I PRINTOUT DATE 2014-03-27
r3
Temperature control method, the parameter set as follows:
00 normal control
01 the temperature is controlled in accordance with the evaporator
sensor measurements; the programmed temperature and D0, D1, D2 i
D3 parameters pertain to the evaporator sensor and the chamber
sensor measurements are displayed.
00
01
1
00
r5
Defrosting activation conditions during the unit start.
00 operation commencement without defrosting
01 if the power failure has occurred during defrosting, the defrosting
process will be activated
02 defrosting after each power supply activation.
00
02
1
00
r6
Door opening sensor option.
00 no door opening sensor present
01 door opening sensor available, connected when door is open
02 door opening sensor available, disconnected when door is open
00
02
1
01
r7
Lighting system activation method
01 only door sensor assisted lighting system control
02 only pushbutton assisted lighting system control
03 door sensor and pushbutton assisted lighting system control
01
03
1
03
r8
Time from the door opening to the alarm activation.
The dr” symbol will be displayed 30 seconds after opening of the door. If
the controller has been equipped with a buzzer, a short sound signal is
emitted, repeated every 30 seconds.
When the time as specified by the R8 parameter has elapsed, the alarm
will be activated and signalled through the dr” symbol blinking on the
display, and, if the buzzer is present in the controller, the sound signal
will be emitted. The compressor will be stopped.
0 denotes the immediate alarm activation
0
20
1min
1min
r9
Place where the door opening sensor is installed:
01 sensor connected to the module accommodating relays
00 sensor connected to the control module Note: A special cable
with a plug should be ordered !!!
00
01
1
01
IX. CHANGES IN THE CONTROL
Software version 02 for controller G-202-P00.
Parameters added: d6 i r0.