Page 16 Service Manual for Producers SCCB TYPE GC203
PPUH „GECO” EDITION I PRINTOUT DATE 2018-07-26
00 - normal regulation
01 - the temperature is adjusted according to the measurement from
the evaporator sensor, the programmed temperature and the
parameters d0, d1, d2 and d3 refer to the evaporator sensor, the
measurement from the chamber sensor is displayed.
Conditions of switching on of defrosting when the unit is switched on:
00 – beginning of operation without defrosting
01 – if during defrosting power supply is disconnected, defrosting will be
switched on
02 – defrosting after every switching on of unit power supply
Option of door opening sensor or additional temperature sensor
00 - no door open sensor
01 - there is a door open sensor closed with the door open
02 - there is a door open sensor open when the door is open
03 – there is a temperature sensor (thermometer)
The method of switching on the lighting
01 - light control only via the door sensor
02 - light control only with the button
03 - light control via door sensor and button
Time from the moment the door is opened to the alarm switching on.
After 30 seconds from the door opening, the word "dr" is displayed and
a short beep is heard, which is repeated every 30 seconds.
After the time r8 has elapsed, the alarm will be activated by flashing the
display with the word "dr" and an audible signal, and the compressor is
switched off.
0 - means immediate activation of the alarm