EasyManuals Logo

gefran 4T72 User Manual

gefran 4T72
7 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #5 background imageLoading...
Page #5 background image
TRAFO 1 TRAFO 5
WSK-0-0-0
Interface cables
+ CD Winstrum
ORDER CODE
time
Alarm
setpoint
Output
Alarm
F.0 = 1
DON = Delayed activation
F.0 = 2
DBI = Delay in turning on output after output is
turned off
time
time
time
F.0 = 3
DOF = Delayed deactivation
F.0 = 4
DP0 = Delayed activation
only at power-on
Variable
rA rA
t < rA
Alarm
setpoint
Output
Alarm
Variable
rA
t < rA
t > rA
Alarm
setpoint
Output
Alarm
Variable
Alarm
setpoint
Output
Alarm
Variable
rA
rA rA
rA
The diagrams refer to a normal absolute alarm with hysteresis H = 0
Filter - outputs with reference to parameters F.0 and r.A
TRAFO 5
10VA, 230/24Vac transformer
TRAFO 1
3VA, 230/24Vac transformer
NTC
PTC / NTC
Transformer
RS323 interface cable for
configuration
7 ACCESSORIES
25 ±1
Ø 7 ±0,5
5,50m
PTC 7 x 25 5m
ORDER
CODE
TECHNICAL DATA
Mod. probe: Ambient probe
Cap material: Plastic (Ø 7 x 25mm)
Temperature range: -20...80°C
PTC: R 25°C = 1K ±1%
(KTY 81-110)
Response time: 20sec (in still air)
Isolation: 100M, 500Vdc
between cap and terminals
Wire material: Unipolar in PVC (12/0,18)
Wire length: 5,50m
ORDER CODE
Conform to VDE 0551, EN 60742, CE
TRAFO 5:
L: 51,5mm,
B: 52,5mm,
H: 35mm
TRAFO 1:
L: 44,5mm,
B: 46,2mm,
H: 32,5mm
Size
N.B.:
the PC configuration
cable is supplied with the
programming software.
Make the connection with
the device powered and
with inputs and outputs
disconnected.
Installation notes
Always power the devices by means of the TRAFO1 transformers specified in the manual (one for each device) when:
The application is unknown.
Multiple devices have input signals that are not isolated from one another, such as, for example: non-isolated grounded thermocouples, transducers or transmitters
powered by a single supply, linear inputs with voltage or current not isolated from one another.
It is a general rule that devices with shared signals (probes, transmitters, signal retransmission, etc.) must be powered by a separate transformer for each device.
Any special cases not covered by the above example must be evaluated from time to time.
One possible example of a power supply by a single transformer is the case of devices with RTD or PTC probes, with relay or logic outputs connected to individually
isolated devices (such as GTS static groups).
ATTENTION: in case of an input with a NON-isolated grounded thermocouple, the secondary of the power transformer for the device CANNOT be grounded: doing so
will cause the device to fail, with probable blowing of the internal fuse.
5
81606B_MHW_4T72_0609_ENG
5 / 7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the gefran 4T72 and is the answer not in the manual?

gefran 4T72 Specifications

General IconGeneral
Brandgefran
Model4T72
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals