Example 2. Periodic cycle Run.
Mode: 06- 00=2or5
The inverter will repeat the same cycle periodically.
All other Parameters are set same as Example 1. shown above.
05-01
06-01
06-02
06-03
05-01
06-01
06-02
06-03
06-16 06-17 06-18
06-19
06-16
06-17
06-18
06-19
T
Hz
RUN
Command
RUN
ON
S1 to S5 auto
Run enable
Example 3. Auto_Run Mode for Single Cycle 06-00=
3 or 6
The speed of final step will be held to run.
Auto Run Mode. 06- 00 =3or6
Frequency 05- 01 =15Hz, 06- 01=30Hz, 06- 02=50Hz, 06- 07=20Hz,
Sequence Run Time 06-16 =20s, 06-17=25s, 06-18=30s, 06-23=40s,
Direction 06-32 =1FWD 06-33=1, 06-34 =1, 06-39=1,
Unused Sequence Parameters 06-03~06- 06=0Hz, 06-19~06-22=0s, 06-35~06-38 =0
05-
01
06-01
06-02
06-16 06-17 06-18 06-23
Hz
06-07
T
RUN
Command
RUN
RUN
S1 to S5 auto
run enable