4-62
08- Protection function group
08- 00
Trip Prevention Selection
Range
xxxx0:Enable Trip Prevention During Acceleration
xxxx1
:Disable Trip Prevention During Acceleration
xxx0x
:Enable Trip Prevention During Deceleration
xxx1x
:Disable Trip Prevention During Deceleration
xx0xx
:Enable Trip Prevention in Run Mode
xx1xx
:Disable Trip Prevention in Run Mode
x0xxx
:Enable over voltage Prevention in Run Mode
x1xxx:Disable over voltage Prevention in Run Mode
08- 01
Trip Prevention Level During Acceleration
Range
50 ~ 200
%
Trip prevention adjustment level during acceleration to prevent over current (OC-A) trips.
If trip prevention during acceleration is enabled and an over current occurs due to the load, then
the acceleration is interrupted until the over current level is dropped below the setting in 08-01
then the acceleration is resumed.
08- 02
Trip Prevention Level During Deceleration
Range
50 ~ 200
%
Effective in SLV mode only.
Trip prevention adjustment level during deceleration to prevent over Voltage (OV-C) trips.
If trip prevention during deceleration is enabled and an over voltage occurs during stopping due
to the load, then the deceleration is interrupted until the over voltage level is dropped below the
setting in 08-02 then the deceleration is resumed.
08- 03
Trip Prevention Level during continuous Run Mode
Range
50 ~ 200
%
Trip prevention adjustment level during continuous Run to prevent over current (OC-C) trips.
If trip prevention during continuous Run is enabled and an over current occurs due the load
such as a sudden transient load, then the output frequency is reduced by decelerating to a
lower speed until the over current level is dropped below the preset in 08-03, then the output
frequency accelerates back to the normal running frequency.
08- 04
Over voltage Prevention Level during Run Mode
Range
200:350~390VDC
400:700~780VDC
Over voltage prevention level can be set by parameter 08-04 when necessary.
When the DC bus voltage is higher than 08-04, inverter will keep running, the output frequency
will be decreased once the DC bus voltage reduced. It’s the over voltage prevention function,
inverter will not appear any error message.
(If the DC bus voltage higher than OV protection level, inverter will appear “OV” message).
08- 05
Electronic Motor Overload Protection Operation Mode(OL1)
Range
xxxx0: Disable Electronic Motor Overload Protection
xxxx1: Enable Electronic Motor Overload Protection
xxx0x: Motor Overload Cold Start
xxx1x: Motor Overload Hot Start
xx0xx: Standard Motor
xx1xx: Invertor Duty Motor ( Force Vent)