4-67
High Speed
(60
Hz
)
Hot Start
116% 150
% 200
%
Motor Load Current (%)
(02-01 = 100%)
Overload Protect Time (min)
1.7
3.9
28.8
start activacted point
High Speed
(60Hz
)
Cold Start
116% 150% 200%
Motor Load Current (%)
(02-01 = 100%)
Overload Protect Time (min)
2.7
6.1
45.2
start activacted point
When 08-19=1:
Low Speed
(
1
.5 Hz
)
Hot Start
100% 150% 200%
Motor Load Current (%)
(02-01 = 100%)
Overload Protect Time (min)
1.7
3.2
8.9
Cold Start
100% 150% 200%
Motor Load Current (%)
(02-01 = 100%)
Overload Protect Time (min)
2.8
5.3
14.9
Low Speed
(1.5 Hz)
High Speed
(60Hz)
Hot Start
116% 150% 200%
Motor Load Current (%)
(02-01 = 100%)
Overload
Protect Time (min)
1.9
4.2
30.9
start activacted point
High Speed
(60
Hz
)
Cold Start
116% 150% 200%
Motor Load Current (%)
(02-01 = 100%)
O
ver
loa
d Pr
ote
ct
Tim
e (m
in)
3.2
7.1
51.6
start activacted point
When 08-19=2:
Low Speed
(1.5 Hz)
Hot Start
100% 150% 200%
Motor Load Current (%)
(02-01 = 100%)
Overload Protect Time (min)
1.9
3.5
9.9
Cold Start
100% 150% 200%
Motor Load Current (%)
(02-01 = 100%)
Overload Protect Time (min)
3.4
6.3
17.8
Low Speed
(1.5 Hz)
High Speed
(60Hz)
Hot Start
116% 150% 200%
Motor Load Current (%)
(02-01 = 100%)
Overload Protect Time (min)
2.1
4.7
34.4
start activacted point
High Speed
(60Hz)
Cold Start
116% 150% 200%
Motor Load Current (%)
(02-01 = 100%)
O
ver
load Protect Time (min)
3.8
8.5
61.9
start activacted point
Motor overload curves (for general motor)