4-78
Example: Regeneration prevention during constant speed.
Set value of 11-14
t
t
Regeneration prevention at work
Vpn(DCV)
Output
frequency
Hz
Example: Regeneration prevention during deceleration.
t
t
Vpn(DCV)
Output
frequency
Hz
Set value of 11-14
Regeneration prevention at work
11-14
Regeneration Prevention Voltage Level
Range
200V: 300.0~400.0 V
400V: 600.0~800.0 V
Regeneration prevention voltage level: if the DC bus voltage level is set too low, then
over-voltage protection will not be reached, but the actual deceleration time will be
extended.
11-15
Regeneration Prevention Frequency Limit
Range
0.00~15.00Hz
Sets the regeneration prevention frequency limit.
11-16
Regeneration Prevention Voltage Gain
Range
0~200%
11-17
Regeneration Prevention Frequency Gain
Range
0~200%
Parameters 11-16 & 11-17 can be used to enhance the response of the regeneration
prevention control, Excessive adjustment could lead to output frequency instability.
If decreasing the setting of parameter 11-16 is not correcting the output frequency instability
then try decreasing the parameter 11-17.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the gefran BDI50-3055-KBX-4-NP-F and is the answer not in the manual?

gefran BDI50-3055-KBX-4-NP-F Specifications

General IconGeneral
Brandgefran
ModelBDI50-3055-KBX-4-NP-F
CategoryInverter
LanguageEnglish

Related product manuals