4-31
100
B
C
1 2.5/3.0 50/60
(V)%
Hz
01-10
01-11
V/F start Frequency
Range
0.00 ~10.00
Hz
VF Start Frequency is for occasion where Start Frequency higher than zero Hz is needed.
01-12
No-load oscillation suppression gain
Range
0.0~200.0%
In V/F mode , If in no load condition current oscillation occurs causing motor vibration then adjust
parameter 01-12 to reduce this effect.
Adjustment can be done in steps of 5 to 10%.
01-13
Motor Hunting Prevention Coefficient
Range
1~8192
01-14
Motor Hunting Prevention Gain
Range
0~100%
01-15
Motor Hunting Prevention Limit
Range
0.0~100.0%
In V/F mode, parameters 01-13,01-14 & 01-15 are used to prevent motor hunting by adjusting the
V/F output voltage level.
01-13 Sets the hunting prevention response time constant (in msecs).
01-14 Sets the Gain of the hunting prevention.
01-15 Sets the hunting prevention voltage limit.
Diagram below shows the Parameter relationships.
01- 16
Auto-Torque Compensation Filter Coefficient
Range
0.1 ~ 1000.0ms
01- 17
Auto-torque Compensation Gain
Range
0~ 100%
01- 18
Auto-torque Compensation Frequency
Range
1.30 ~ 5.00Hz
Auto-torque Compensation function is effective in V/F mode. It can be used to correct insufficient
torque at low frequencies ( below 5 hz)
Parameters 01-16 to 01-18 are effective after carrying out Auto tune function in SLV mode.
Setting 01-17=0 Disables the auto torque compensation function.