12  ADV50 QS, SW-PW V1.11 / CTL V2.11 
Italiano  English 
Italiano  English 
Pr.  Explanation  Settings 
Factory 
Setting
NOTE 
01.24 
Delay Time at 40Hz 
for Simple Position 
0.00 to 600.00 sec  0.00   
01.25 
Delay Time at 50Hz 
for Simple Position 
0.00 to 600.00 sec  0.00   
01.26 
Maximum Voltage 
Frequency (Fbase) 
(Motor 1) 
0.10 to 600.0 Hz  60.00   
115V/230V series: 0.1V to 255.0V  220.0   
01.27 
Maximum Output 
Voltage (Vmax) 
(Motor 1) 
460V series: 0.1V to 510.0V  440.0   
01.28 
Mid-Point Frequency 
(Fmid) (Motor 1) 
0.10 to 600.0 Hz  1.50   
115V/230V series: 0.1V to 255.0V  10.0   
01.29 
Mid-Point Voltage 
(Vmid) (Motor 1) 
460V series: 0.1V to 510.0V  20.0   
01.30 
Minimum Output 
Frequency (Fmin) 
(Motor 1) 
0.10 to 600.0 Hz  1.50   
115V/230V series: 0.1V to 255.0V  220.0   
01.31 
Minimum Output 
Voltage (Vmin) (Motor 
1) 
460V series: 0.1V to 510.0V  440.0   
01.32 
Maximum Voltage 
Frequency (Fbase) 
(Motor 2) 
0.10 to 600.0 Hz  60.00   
115V/230V series: 0.1V to 255.0V  220.0   
01.33 
Maximum Output 
Voltage (Vmax) 
(Motor 2) 
460V series: 0.1V to 510.0V  440.0   
01.34 
Mid-Point Frequency 
(Fmid) (Motor 2) 
0.10 to 600.0 Hz  1.50   
115V/230V series: 0.1V to 255.0V  10.0   
01.35 
Mid-Point Voltage 
(Vmid) (Motor 2) 
460V series: 0.1V to 510.0V  20.0   
01.36 
Minimum Output 
Frequency (Fmin) 
(Motor 2) 
0.10 to 600.0 Hz  1.50   
115V/230V series: 0.1V to 255.0V  10.0   
01.37 
Minimum Output 
Voltage (Vmin) (Motor 
2) 
460V series: 0.1V to 510.0V  20.0   
01.38 
Maximum Voltage 
Frequency (Fbase) 
(Motor 3) 
0.10 to 600.0 Hz  60.00   
115V/230V series: 0.1V to 255.0V  220.0   
01.39 
Maximum Output 
Voltage (Vmax) 
(Motor 3) 
460V series: 0.1V to 510.0V  440.0