.... Instruction manual
VDI Modbus
Communication Protocol

Other manuals for gefran VDI100

Questions and Answers

  • J
    Jennifer WallaceSep 12, 2025
    What does STO Run Permissive mean on Gefran Inverter?
    • K
      kirbyhollySep 12, 2025
      If a Gefran Inverter displays an 'STO Run Permissive' error, it could be due to: * Terminal board Input F1 and F2 are not connected. To resolve this: * Check F1 and F2 connection.
  • R
    Rose PattonSep 12, 2025
    What to check if Gefran Inverter displays SS1 Digital input Stop command?
    • M
      Michelle BurnsSep 12, 2025
      If a Gefran Inverter displays an 'SS1 Digital input Stop command' error, it could be due to: * 08-30 =0 and 03-00~03-07=58. To resolve this: * Check if 08-30 =0 and 03-00~03-07=58.
  • C
    Curtis RushSep 12, 2025
    What causes FB PID feedback loss on Gefran Inverter?
    • B
      brian16Sep 12, 2025
      If a Gefran Inverter displays an 'FB PID feedback loss' error, it could be due to: * Feedback signal wire broken. * Feedback sensor broken. To resolve this: * Check feedback wiring. * Replace feedback sensor.
  • K
    Kimberly ThomasSep 9, 2025
    How do I fix CE communication error on Gefran Inverter?
    • J
      Jessica NelsonSep 9, 2025
      If a Gefran Inverter displays an 'CE communication error', it could be due to: * Connection lost or wire broken. * Host stopped communicating. To resolve this: * Check connection. * Check host computer / software.
  • T
    Tanya WalkerSep 8, 2025
    What to do if Gefran Inverter displays run Switch for Motor1/ Motor2 error?
    • C
      Courtney SmithSep 9, 2025
      If a Gefran Inverter displays an 'run Switch for Motor1/ Motor2' error, it could be due to: * Executing a command for switching motor2 in running time. * Executing a command for switching motor in running time. To resolve this: * Revise the sequence control and switch motor in top time.
  • M
    Melissa DixonSep 7, 2025
    What causes DEV Speed deviation on Gefran Inverter?
    • K
      Kimberly KingSep 7, 2025
      If a Gefran Inverter displays an 'DEV Speed deviation' error, it could be due to: * Load being too heavy. * Mechanical brake active preventing motor from turning. * PG wiring error. * PG parameters (group 20) set incorrectly. * Acceleration / deceleration time set to short. To resolve this: * Check load. * Make sure brake is released. * Check PG wiring. * Check PG parameters 20-23/20-24. * Increase Acceleration / deceleration time.
  • B
    Bethany EdwardsAug 23, 2025
    How to fix OC over current on Gefran Inverter?
    • L
      leejoelAug 23, 2025
      If the Gefran Inverter displays an 'OC over current' error, it could be due to several reasons: * Acceleration or deceleration time being too short. * A contactor being present on the inverter's output side. * The motor being used is either a special type or its size exceeds the inverter's rated capacity. * A short circuit or ground fault. To resolve this, try the following: * Extend the acceleration or deceleration time. * Check the motor wiring. * Disconnect the motor and attempt to run the inverter.
  • A
    Amanda WalkerSep 5, 2025
    What causes OS Over speed on Gefran Inverter?
    • E
      elizabeth71Sep 5, 2025
      If a Gefran Inverter displays an 'OS Over speed' error, it could be due to: * Motor speed overshoot (ASR). * PG ppr set incorrectly. * Overspeed parameters set incorrectly. To resolve this: * Check ASR parameters group 21. * Check PG parameters. * Check overspeed parameters 20-20/20-12.
  • C
    christopherramosSep 5, 2025
    What does UT Under torque detection mean on Gefran Inverter?
    • L
      Lauren BellSep 5, 2025
      If a Gefran Inverter displays an 'UT Under torque detection' error, it could be due to: * Sudden drop in load. * Belt break. To resolve this: * Check under torque detection parameters (08-19 / 08-20). * Check load / application.
  • A
    Andrew DiazSep 4, 2025
    What causes OT Over torque detection on Gefran Inverter?
    • T
      Tina CooperSep 4, 2025
      If a Gefran Inverter displays an 'OT Over torque detection' error, it could be due to: * Load being too heavy. To resolve this: * Check over torque detection parameters (08-15 / 08-16). * Check and reduce the motor load, also check the operation duty cycle.

Summary

Modbus Protocol Descriptions

Communication Connection and Data Frame

Details Modbus network connection, pinouts, and ASCII data frame structure.

Modbus RTU Data Frame and Checksum

Explains Modbus RTU data frame structure, checksum calculation (LRC and CRC).

Modbus Communication Error Codes

Details Modbus communication error codes for ASCII and RTU modes, including exception codes.

Register and Data Format

Defines register numbers, formats for command and monitor data, and their structure.

Modbus Commands: Read Holding Register and Loop Back Test

Explains Modbus commands for reading registers (03H) and loop back testing (08H).

Modbus Commands: Write Single and Multiple Registers

Details Modbus commands for writing single (06H) and multiple registers (10H).

Parameter Data Reference

Lists Modbus parameters with their corresponding functions and register numbers for various groups.