Valve
can be
opened and closed.
Switching message after connecting
the supply voltage
without default setting
Automatic
Manual
= automatic initialization
The product is
ready for operation and reacts
to the externally
specified set value.
In the case of the
"Process controller" option,
this must be activated
separately.
Press twice
Automatic initialization
Manual initialization
The product is
ready for operation and reacts
to the externally
specified set value.
In the case of the
"Process controller" option,
this must be activated
separately.
Press twice
* In the "adjTime" step, the determined travel time of the valve is displayed for
both directions (open/close). To change the travel time, this step can be
interrupted by pressing the -> key ("adjust nozzle(s)" display) and influenced via
the pneumatic throttles at the rear. Fine adjustment is carried out by repeating the
travel time measurement several times and sequentially changing the throttle
position. If values of <1.0 sec. are displayed, it is strongly advisable to use the
throttles. Travel times of >1.0 sec. are recommended in order to achieve optimal
control results
-> See also chapter "Throttle settings"
*
*