www.gemu-group.com66 / 76GEMÜ 1436 cPos
17 Troubleshooting
No. Error message Description Condition for the occurrence
of the error
Error cause
201 Intern. error
Information
An error has occurred
with an EEPROM.
This information is displayed
if an error has occurred
while attempting to access
an EEPROM.
The message is generated if an
EEPROM could not be read from
or written to. Send the controller
to GEMÜ for repair.
Error message Description Condition for the occurrence
of the error
Error cause
In 1 no Signal No signal at digital input
In 1
Parameter In 1 is set to OFF /
ON or Safe / ON
Connect signal to digital input In
1
In 2 no Signal No signal at digital input
In 2
Parameter In 2 is set to OFF /
ON or Safe / ON
Connect signal to digital input In
2
In W no Signal No signal at digital input
In W
Parameter In W is set to
OFF / ON or Safe / ON
Connect signal to digital input In
W
In X no Signal No signal at digital input
In X
Parameter In X is set to
OFF / ON or Safe / ON
Connect signal to digital input In
X
All error messages can be read in the menu item ErrorList (1 Service / 1.3 Diagnosis).
The menu item ClearErrorList (1 Service / 1.3 Diagnosis) can be used to clear the internal error memory.
Occurrence of the error in the "NoInit" menu:
The error message is displayed in the "NoInit" menu. Pressing the or key switches off the display of the error, and
"NoInit" appears with the display of the current valve position. The valve can be moved by pressing the and keys.
The error message is displayed again when the action is complete. To end the action, the menu must be exited by pressing the
or key.
Setup
NoInit XX.X%
060: TrvlSensErr
Setup