EasyManua.ls Logo

geminox THR 10-100 Series - Commissioning

geminox THR 10-100 Series
92 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...

&200,66,21,1*
 &200,66,21,1*
Activate the boilers external electrical circuit-break-
er.
During initial commissioning, the heating engineer
must check:
- the correct operation of each module,
- the correct operation of RVA control.
 &RQWURORIHDFKPRGXOH¶VRSHUDWLRQ
- activate the On/Off switches (item no. 10) of each
module.
- an LGM self-regulation phase of each module be-
gins and signals /3& appear in succession
on the displays (item no. 4) then and finally 2.
Note:
- The alarm indicator (item no. 6) is on:
manually reset button (item no 8),
if the alarm continues, refer to the operating
fault list paragraph 1 - section XI - OPERA-
TING FAULTS.
- Check the setting of the burners. The burners are
preset for natural gas H (G20). However, during
commissioning, separate CO2/CO combustion
verifications must be carried out on each module
(paragraph 3 - section VII - COMBUSTION CON-
TROL).
 &KHFNLQJ59$FRQWURO
 3DUDPHWHUVHWWLQJ
- The basic THR 10-100 requires no specific pro-
gramming. The RVA 47 is preprogrammed.
- When the RVA 46 option is integrated into the
THR 10-100, the THR 10-100 requires program-
ming (paragraph 5 - section VIII - MULTICIRCUIT
WITH A THR 10-100),
- Set the time and day on regulator RVA 47:
(see paragraph 3.3 - section III - INSTALLATION
from the RVA 47 technical instructions)
: time setting,
: day setting.
Note:
- if one or several RVA 46s are connected to the
master RVA 47, their time and day are automati-
cally updated.
 &RPPXQLFDWLRQFRQWURO
 3DUDPHWHUFRQWURO
- Check that the following parameters do not indi-
cate any errors. If the displays differ from the dis-
plays in the following tables, see section XI -
OPERATING FAULTS.
)ROORZLQJ WKH HOLPLQDWLRQ RIWKHIDXOW
HUURUPHVVDJH(URQWKH59$PD\
WDNHWR PLQXWHVWRGLVDSSHDUDF
FRUGLQJWRWKHW\SHRIIDXOW
- Also check the location of the outside sensor and
if necessary test the inputs/outputs of each regu-
lator.
4 10

4 10
8 6
8 6
)LJ
59$5HJXODWRUSDUDPHWHUV 'LVSOD\
: display of BMU (LGM) error
codes
- - -
: error display
blank
: display of PPS communication
selection of PPS addresses using
buttons +/-
4 102
5 102
59$5HJXODWRUSDUDPHWHUV 'LVSOD\
: display of BMU (LGM) error
codes
blank
: error display
blank
:
display of PPS communication
if room sensor on RVA 46
- - -
or
1 83
!

Related product manuals