9,,,08/7,&,5&8,7:,7+$7+5 
 *(1(5$/32,176
ALBATROS regulators can be connected to one
another to meet the demand of the market for com-
plete and complex installation regulation.
Parameters must be set as indicated in the table of
the standard installation diagram.
The RVA 47 is the master regulator.
Time and day
setting is carried out on the RVA 47 only. The time
and day are automatically transmitted to all the other
connected RVA 46 regulators as well as to all the
QAA 70 room sensors.
7KHDXWRPDWLFVZLWFKLQJVHWWLQJRIWKH
/*0DQG59$UHJXODWRUVPXVWEHIL[HG
DW WKH VDPH YDOXH 7KH\ DUH VXSSOLHG
ZLWK YDOXH  & :LWK WKH /*0 WKLV
VHWWLQJFDQRQO\EHPRGLILHGZLWKLQWHU
IDFH$=:
Two RVA 46s can be integrated into the RVAs con-
trol panel in order to control two heating circuits
(pump circuit or mixer valve circuit). The connection
of this option (RVA 46 for THR 10-100) is made
easier with prewiring (communication bus, power
supply) - (see paragraph 3 - section VIII - MULTI-
CIRCUIT WITH A THR 10-100 and the RVA 46 ins-
tallation instructions for THR 10-100 ).
To control more than two heating circuits, it is nece-
sary to connect as many ZH 46 control boxes as ad-
ditional heating circuits.
&20081,&$7,2135,1&,3/(
In order to ensure correct communication between
each regulator, each RVA (RVA 47 and RVA 46)
must be addressed (see paragraph 4 - section VIII -
MULTICIRCUIT WITH A THR 10-100).
By default:
- the heat production regulators (RVA 47) must be
on segment 0,
- the heat distribution regulators (RVA 46) must be
on a segment situated between 0 and 14 (for
example all RVA 46s on segment 1
).
!
'% 0% $ 0'
59$
2&,
/
/
*
*
0
0
5
5
9
9
$
$
ZH 46
ZH 46
To other ZH 46
control boxes
LPB
PPS
59$ 59$ 59$ 59$
2&,
/*0%08

/*0%08

67
67
'% 0% $ 0' '% 0% $ 0' '% 0% $ 0'
'
%0%
$
0
'
0/1 1/1 1/2 1/3 1/4
Addressing of units
Segment/Address
1/...
THR 10-100
)LJ

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the geminox THR 10-100 Series and is the answer not in the manual?