SERVICE SCHEDULE
System / Component
Frequency Procedure
Weekly - W
Monthly - M
Yearly - Y
Inspect Change Clean
Fuel
Fuel Lines & Connections M X
Lubrication
Oil Level M X*
Oil Y X**
Oil Filter Y X**
Cooling
Engine Coolant Lines & Connections M X
Engine Coolant Level M X
Engine Coolant Y X
Enclosure Louvers W X X
Engine
Air Cleaner Y X X***
Spark Plugs Y X X***
Battery
Remove Corrosion, Ensure Dryness M X X
Clean & Tighten Battery Terminals M X X
Check Charge State M X X***
Check Electrolyte Level M X X***
General Condition
Vibration, Noise, Leakage, Temperature M X
Generator System
Complete Tune-up and System Inspection Y To be completed by an Authorized Service Dealer.
Footnotes
* Inspect the oil level monthly or every 12 hours during continuous operation.
** Change oil and oil filter after the first 30 hours of operation and then every 100 hours or annually thereafter, whichever occurs first.
Change sooner when operating under heavy load or in a dusty or dirty environment or in high ambient temperatures.
*** Replace as necessary.
11-1
SrvSchd004 Rev. B 05/10
Service Schedule

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Generac Power Systems 45kW and is the answer not in the manual?

Generac Power Systems 45kW Specifications

General IconGeneral
BrandGenerac Power Systems
Model45kW
CategoryPortable Generator
LanguageEnglish

Related product manuals