Generac Portable Products 6500EXL Extended Life Generator
9
COLD WEATHER
OPERATION
Under certain weather conditions (temperatures below
40°F [4°C] and a high dew point), your generator may
experience icing of the carburetor and/or the crankcase
breather system.
In an emergency, use the original shipping box as a
temporary shelter:
Cut off all flaps.
Cut out one of the long sides of the box to expose
exhaust side of unit. Ensure a minimum of two feet
clearance between open side of box and nearest object.
Cut appropriate slots to access receptacles of unit.
Start unit, then place box over it.
IMPORTANT: Remove shelter when temperature is
above 40°F [4°C].
For a more permanent shelter, build a structure that will
enclose three sides and the top of the generator:
Make sure entire muffler-side of generator is exposed.
Note that your generator may appear different from that
shown in Figure 10.
Ensure a minimum of two feet clearance between open
side of box and nearest object.
Face exposed end away from wind and elements.
Enclosure should hold enough heat created by the
generator to prevent problems.
CAUTION!Neverrun unit indoors. Do Not
enclose generator any more than shown.
RECEPTACLES
120/240 Volt AC, 30 Amp, Locking
Receptacle
Use a NEMA L14–30 plug with this receptacle. Connect a
4–wire cord set rated for 250 Volt AC loads at 30 Amps (or
greater) (Figure 11).You can use the same 4–wire cord if
you plan to run a 120 Volt load.
This receptacle powers 120/240 Volt AC, 60 Hz, single
phase loads requiring up to 3,600 watts of power at
30 Amps for 120 Volts; 6,500 watts of power (6.5 kW) at
30 Amps for 240 Volts.The outlet is protected by a 30 Amp
push–to–reset circuit breaker.
CAUTION! Although this outlet states it has a
240 Volt 30 Amp rating (up to 7,200 watts), the
generator is only rated for 6,500 watts. Powering
loads that exceed the wattage/amperage capacity of
the generator can damage it or cause serious
injuries.
120 Volt AC, 30 Amp Locking
Receptacle
Use a NEMA L5–30 plug with this receptacle. Connect a
3–wire cord set rated for 125 Volt AC loads at 30 Amps to
the plug (Figure 12).
Figure 10 — Temporary Cold Weather Shelter
Wind
Figure 11 — 120/240 Volt AC, 30 Amp, Locking Receptacle