Operation
Volatile liquids are not supplied by General Monitors.
Below is a list of volatile liquids and the volume required
(in microliters) to produce 50% LEL in the 3 liter chamber.
Acetaldehyde 137
Acetic Acid 140
Acetone 113
Acetonitrile 96
Acrylonitrile 121
Amyl Acetate 100
Amylamine 156
Benzene 71
Butyl Acetate 137
Butyl Acylate 132
Butyl Alcohol 79
sec-Butyl Alcohol 95
tert-Butyl Alcohol 139
Butyl Cellosolve 88
Butyraldhyde 103
Cyclohexane 86
Decane 96
Diethyl Ketone 104
Diisobutyl Ketone 82
Dimethylformamide 104
p-Dioxane 105
Dodecane 84
Ether, Ethyl 120
Ethanol (Ethyl Alcohol) 119
Ethyl Acetate 120
Ethyl Amine 140
Ethyl Benzene 75
Ethylene Oxide 91
Gasoline 100 Octane 107
Heptane, Normal 94
Hexane, Normal 87
Isopentane 100
Isoprene 92
Isopropyl Alcohol 94
Isopropyl Ether 121
JP-4 Jet Fuel 183
Laktane 76
Methanol 149
Methyl Ethyl Ketone (MEK) 77
Methyl Metacrylate 112
Naptha (Petroleum Ether) 94
Octane 100
Pentane, Normal 106
Propanol 115
2-Propanol 93
Propyl Acetate 108
Propylamine 101
Propylbenzene 68
Propylene Oxide 99
Styrene 63
Tetradecane 80
Tetrahydrofuran 100
Tetrahydrofurfuryl Alcohol 89
Toluene 71
1,1,1-Trichlorethane 459
Trichloroethylene 440
Triethylamine 103
Vinyl Acetate 147
Vinyl Ethyl Ether 100
o-Xylene 67
p-Xylene 82
Xylenes 83
4.2 Digital Display Codes
The following codes will appear on the dis-
play when the unit is placed in a mode other
than the normal operating mode.
SU Start-Up
- - (steady) Magnetic Switch Activated
- - (flashing) Test Gas Mode
AC Automatic Calibration
CP Calibration in Progress
CC Calibration is Complete
F1 Failed to Zero during calibration
F2 Failed to complete the calibration
F3 Failed to Span during calibration
F4 Sensor Reference Bead Error
F5 Sensor Active Bead Error
F6 Low Supply Voltage
F7 EEPROM Verification Failure
F8 Negative Zero Drift
F9 Calibration check period exceeded
When the unit is in the normal operating
mode, the display will indicate the presence of
combustible gas in percent of the Lower Ex-
plosive Level (% LEL). The range of detec-
tion is from 0 to 99% LEL.
99 (
flashing) Over-Range, a gas concentration
exceeding 100% LEL is present.
SU This is displayed for about fifty seconds
during start-up and after a Fault condition
has been corrected.
- - Appears on the display when the magnet
has been properly positioned over the
GMI Logo and when the Test Gas
Mode can be or has been entered.
14
GENERAL MONITORS
Model S104