465mm
8080
195 195 195
305mm
boiler
wallbracket
21
Theheatingsystemmustincludeaproperfilter.Toutilizethemaximumoutputofthe
boileritisnecessarytoensureminimumpressureintheheatingsystemof0,8barforright
operationandlonglifetime.Abuiltexpansiontankenablesconnectingtheboilertothe
closedheatingcircuit.Theboileristooperateonnaturalgasof20mbarnominalpressureor
LPGof37mbarnominalpressureinthedistributionnet.Theboilerislocatedsoastoensure
necessaryoperatingconditionswithregardtothewaysofcombustionairsupplyandwaste
gasexhaust.
Localizationofboilersmustsuittoprojectdocumentation.Boilersaretobesituatedinthe
waytoensurealltheoperationconditionsneededandwithregardtothewayofcombustion
airsupplyandwastegasexhaust.Fromthesidesofboilerstheremustbefreeaccessofat
least0.2mandinfrontofboilers1mforassemblyandservice.Boilersmustbeinstalledat
least0,1moverthefloor.
Mountingtheboilersonthewallmustbeperformedonthebaseofqualifiedassessmentof
thewallbearingcapacity(byaprojectworkerorassemblycompany)soastoguaranteesafe
andreliablehangingofboilers.Theboilerhangsonawallbracketwhichmustbemounted
tothewallwithasuitableconnectingmaterial(e.g.screwsanddowels)regardingthequality
ofthewallandweightoftheboiler.
Condensateproducedduringtheoperationoftheboilermustbedrainedoffconstantly.The
diameteroftheoutletsystemmustbeatleast13mm.Fortheoutletofcondensatetosewage
itisnecessarytofollowproperlocalandnationalrules.Ifneeded,neutralizationdevicecan
beused.Condensatecannotbegatheredinanycase,thereforetheoutletmustbeinmin.
slopeof3%tosewagedownwardsfromtheboiler.
Localizationofboilers
Mountingtheboilersonthewall
Condensateoutlet